Plan Review Notes
Plan Review Notes For Permit 07010448
Permit Number 07010448
Review Stop G
Sequence Number 2
Notes
Date Text
2007-04-25 18:42:53DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM THE PREVIOUS REVIEW:
  
 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, NOT ADDRESSED
  
 C. N/A
 D. N/A
 E. OK
  
 ****NEW COMMENT:
  
 1B. 1" PIPE AND VALVE ARE REQUIRED TO THE APPLIANCES
 WITH 105 CFH AND 108 CFH PER TABLE 402.4(2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]