Plan Review Notes
Plan Review Notes For Permit 07010448
Permit Number 07010448
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-02 10:44:19** UNSAT2ND REVIEW **
  
 1) NOTE:PLEASE SEE PLANS ARE NOW INDICATING A
 COMPLETE NEW PROPOSED SERVICE WHICH AT THIS TIME DOES
 NOT MEET 230.2 AND IS NOT GRANTED.
 PLEASE SEE THAT THE LANDLORD SERVICE WILL BE REQUIRED
 TO BE UPGRADED.
 PLEASE SEE THE RISER SHOWS FEEDS FROM THE FPL
 TRANSFORMER HOWEVER TWO SEPARATE VOLTAGES ARE ALSO
 SHOWN.
 PLEASE ADJUST AND GIVE INFORMATION FOR EXISTING SERVICE
 TO BE UPGRADED.
  
 2) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THE
 PLANS.PLEASE SEE THE LIGHTING POWER DENSITIES FOR
 MANY OF THE AREAS EXCEED THAT OF WHICH IS SHOWN ON
 TABLES IN THE FBC.
 PLEASE SEE THE RESPONSE MENTIONS THAT OCCUPANCY SENSORS
 ARE TO BE INSTALLED, HOWEVER THESE COULD NOT BE LOCATED
 ON PLANS.
 PLEASE SEE THE DETAIL SUBMITTED SHOWS MANUAL SWITCHES
 AFTER THE OC DEVICE, WHICHIF THE SWITCH IS IN THE OFF
 POSITION WOULD NO ALLOW ANY USE OF THE AUTOMATED MEANS
 AS REQUIRED.
 PLEASE PROVIDE MORE INFORMATION FOR THE LIGHTING
 CONTROLS. THE SWITCHES BEING NOTED AS SENSOR TYPES DOES
 NOT PROVIDE THE COVERAGE NEEDED.
 PLEASE SEE 13-415.2.ABC.1.2 AND PLEASE THE AMOUNT OF
 THE WATTAGE ON TRANSFORMERS NEEDS TO BE SPECIFIED.
 PLEASE SEE THE LIMITS ON TRACK.
 PLEASE VERIFY THE METHOD WHICH IS BEING USED.
 ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED NEEDS
 THE SEAL TO BE CLEAR AND VISIBLE WITH ALL INFORMATION
 ON SAID SEAL.
 13-103.1.1.1 FS 471.025
  
 3) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS FOR
 SHOW WINDOWS WERE DERIVED. (X-AMOUNT OF FEET TIMES
 200VQA PER FT =Y). PLEASE PROVIDE IN THE SUMMARY HOW
 RECEPTACLE LOAD WAS DERIVED. (X AMOUNT OF DEVICES TIMES
 180VA=?).
 PLEASE SEE THE LOAD SUMMARY WAS REVISED, HOWEVER COULD
 NOT LOCATE THELOAD OF 200VA PER FT ADDED FOR WINDOW
 AREAS.
 220.43, 220.44 ETC.
 FBC 106.1.2, 106.3.5.1.2.
  
 4) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS A
 GENERAL NOTE FOR THE FS 553.80(2)(B).IT IS UNCLEAR
 WHY THIS COMMENT HAS BEEN MADE AS THERE NOTHING THE
 REVIEW COMMENTS FROM PLAN REVIEW WHICH REFERENCED THIS
 FS.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-31 18:37:36IN ELEC FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved