Plan Review Notes
Plan Review Notes For Permit 07010448
Permit Number 07010448
Review Stop P
Sequence Number 1
Notes
Date Text
2007-02-08 14:13:56DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 WEST PALM BEACH CITY CODE
  
 1. COVER SHEET INDICATES THAT THE KITCHEN AREA IS
 1,313SF, THE DINING UNCONCENTRATED 210SF, AND THE
 DINING FIXED SEATING 107SF. THIS TOTALS 1,630SF. THE
 FLOOR PLAN SHT A-1 AND THE APPLICATION INDICATE A GROSS
 SF OF 3,511SF, WHICH LEAVES 1,941 SF UNACCOUNTED FOR.
 PLEASE CLARIFY. PLEASE CONFIRM THE MINIMUM REQUIREMENTS
 PER TABLES 1004.1.2 AND 403.1. INDICATE ALL
 OCCUPANCIES, (STORAGE, BUSINESS ETC.), THAT MAY BE
 LOCATED WITHIN THE RESTURANT. PLEASE KEEP IN MIND THAT
 POTTY PARITY MAY BE REQUIRED DEPENDING ON THE NUMBER OF
 WATER CLOSETS/URINALS REQUIRED IN THE MEN'S TOILET
 ROOM. SECTION 403.1.1.
  
 2. SHT A-3 (49 SEATS NOT COUNTING THE BENCH SEATING).
 INDICATE THE LENGTH OF EACH BENCH. PER SECTION 1004.7,
 THE OCCUPANT LOAD OF SEATING BOOTHS SHALL BE BASED ON
 ONE PERSON FOR EACH 24 INCHES OF BOOTH SEAT LENGTH
 MEASURED AT THE BACKREST OF THE SEATING BOOTH.
  
 3. SHT P-1 THE SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. VENTS ARE REQUIRED FOR THE MOP SINK,
 THE WOMEN'S TOILET ROOM LAV, AND THE 2ND HAND SINK.
 SECTION 901.2.1. THE 3RD HAND SINK REQUIRED BY DBPR
 REVIEW NOTES SHALL BE SHOWN ON THE RISER DIAGRAM.
 SECTION 106.1.1.--THE DISHWASHER SHALL CONNECT TO
 SANITARY, NOT THE GREASE DRAIN AS SHOWN. MUNICIPAL CODE
 SECTION 90-124(7)(B).
  
 4. 1 COPY OF THE TWO PAGE "SPECIFICATION WORKSHEETS"
 SHALL BE ATTACHED TO EACH SET OF PLANS STAMPED REVIEWED
 AND STAMPED BY DBPR PLAN REVIEW.
  
 5. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED,
 APPROVED, AND SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE
 CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER.
 (561) 822-2271, FAX (561) 722-2279, OR E-MAIL
 [email protected]. WASTE ORD. #3434.
  
 6. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL).
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 D. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 E. WHERE WET GAS EXISTS, A DRIP SHALL BE PROVIDED AT
 ANY POINT IN THE LINE OF PIPE WHERE CONDENSATE COULD
 COLLECT. (SEE THE W/H). SECTION 408.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved