Plan Review Notes For Permit 07010448 |
Permit Number |
07010448 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-13 08:08:13 | --------------DENIED-------------- | | | | 1. ROOM 104 SHOWS R/A GRILL IN CEILING WITH NO DUCT | | BACK TO AHU 1. IS THIS TO BE A CEILING PLENUM AREA? | | THIS APPEARS TO BE A DUCTED RETURN SYSTEM. PLEASE | | CLARIFY, SHOWING THE BALANCED RETURN REQUIREMENTS OF | | FBC,M 601.4. PLEASE NOTE: A GAS WATER HEATER VENT SHALL | | NOT BE ROUTED THROUGH A PLENUM PER FBC,M 601.3. | | | | 2. R/A GRILL IN CEILING OF ROOM 106 WHICH IS DUCTED | | BACK TO AHU 1, DUCT SIZE IS MISSING FROM PLAN. PLEASE | | CLARIFY PER FBC 106.1.1. | | | | 3. AUXILIARY DRAIN PAN WITH SECONDARY DRAIN LINE SHALL | | DISCHARGE IN A CONSPICUOUS LOCATION PER FBC,M | | 307.2.3(1). PLEASE PROVIDE DETAIL TO SHOW COMPLIANCE | | WITH THIS REQUIREMENT. | | | | 4. AHU MOUNTING DETAIL REFERS TO PLUMBING DRAWING FOR | | LOCATION OF CONDENSATE DISPOSAL. NO SUCH INFORMATION | | COULD BE FOUND ON PLUMBING DRAWINGS. PLEASE PROVIDE | | INFORMATION NEEDED TO SHOW COMPLIANCE WITH ALL OF | | SECTION 307.2. | | | | 5. ACTUATION OF A DUCT SMOKE DETECTOR SHALL ACTIVATE AN | | AUDIBLE AND VISUAL SIGNAL (HORN AND STROBE) IN AN | | APPROVED LOCATION PER FBC,M 606.4.1(2). | | | | 6. SEPERATE PERMITS/APPLICATIONS ARE REQUIRED FOR | | KITCHEN HOOD, HOOD SUPPRESSION AND WALK-IN | | COOLER/FREEZER. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|