2007-02-08 14:15:04DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL).
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 D. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 E. WHERE WET GAS EXISTS, A DRIP SHALL BE PROVIDED AT
 ANY POINT IN THE LINE OF PIPE WHERE CONDENSATE COULD
 COLLECT. (SEE THE W/H). SECTION 408.2.
  
 REVIEW BY KEN STEVENS