Date |
Text |
2007-02-20 14:36:58 | *****DENIED***** |
| |
| |
| 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 03.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE OR |
| THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES). |
| |
| 04.THE COMPLETE ADDRESS , INCLUDING THE TENANT SPACE |
| NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED |
| PLAN SHEET. |
| |
| 05.ON THE APPROPIATE EXTERIOR ELEVATION DETAIL, |
| DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE.AS PER |
| WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS |
| THAN 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| |
| 06.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| THE TRAVEL DISTANCE TO THE EXIT(S). |
| |
| 07.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR |
| THIS TENANT SPACE.IF THE SPRINKLER SYSTEM IS MODIFIED |
| DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT |
| WILL BE REQUIRED. |
| |
| 08.THE INTERIOR WALL AND CEILING FINISH MATERIALS |
| SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS |
| HAVING OCCUPANT LOADS OF 300 OR FEWER.PLEASE |
| SPECIFY. |
| |
| 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE |
| WITH NFPA 96.SEPARATE PLANS SND PERMIT WILL BE |
| REQUIRED FOR THE COOKING HOOD INSTALLATIN AND THE |
| ASSOCIATED SUPPRESSION SYSTEM. |
| |
| 10.SMOKE DUCT DETECTORS, AS INDICATED ON SHEET M1, |
| SHALL INITIATE A GENERAL FIRE ALARM. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH COMMENT WAS |
| ADDRESSED. |
| |
| |