2007-01-28 18:21:36 | ** UNSAT ** |
| |
| 1) NOTE:PLEASE KNOW AS PROJECT WAS APPLIED FOR PERMIT |
| AFTER DECEMBER 8TH, 2006 THE FOLLOWING CODES FOR DESIGN |
| AND AS REFERENCED ON PLANS HAVE CHANGED. |
| PLEASE KNOW THE STATE HAS NOW ADOPTED THE 2006 |
| REVISIONS TO THE 2004 FBC WHICH HAS CHANGES FOR |
| BUILDING, MECHANICAL, PLUMBING AND CHANGES FOR CHAPTER |
| 13 WHICH WILL AFFECT THE ELECTRICAL PLANS. |
| PLEASE ALSO KNOW THE ELECTRICAL CODE NOT ADOPTED AS OF |
| 12/8/06 IS THE 2005 NFPA-70 (NEC). |
| PLEASE BE SURE THE ARCHITECTURAL PLANS AND MEP'S ARE |
| UPDATED WITH CODE REFERENCES. |
| |
| PLEASE ADJUST PLANS, DESIGNS AND PLEASE BE SURE TO SEE |
| ANY COMMENTS FROM OTHER TRADES WHICH MAY AFFECT THE |
| ELECTRICAL PLANS. |
| |
| 2) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THE |
| PLANS. PLEASE SEE THE CALCULATIONS INDICATE THE |
| CONTROLS FOR LIGHTING AS MANUAL. |
| PLEASE ALSO PROVIDE PERFORMANCE CALCULATIONS PER |
| 13-415.2. |
| PLEASE VERIFY THE METHOD WHICH IS BEING USED. PLEASE |
| SEE THIS IS SUBMITTED AS METHOD *A*WILL THIS |
| INCORPORATE ALL AREAS? |
| ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT |
| SEALED BY THE DESIGNER OF RECORD AS REQUIRED. |
| 13-103.1.1.1 |
| |
| 3) NOTE: PLEASE CORRELATE RISER AND PANEL *A*. PLEASE |
| SEE ONE SHOWS 600A MLO AND THE OTHER ON RISER AS 400A |
| MLO. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 4) NOTE: PLEASE SEE THAT IF ANY FIRE ALARM SYSTEMS ARE |
| REQUIRED AND INSTALLED. PLEASE INDICATE ALL THE MINIMUM |
| LEVELS FOR THESE DEVICES ON PLANS. PLEASE ALSO INDICATE |
| THE LOCATIONS. PLEASE SEE KNOW IF APPLICABLE, THESE |
| WILL BE REQUIREDTO BE SHOWN ON BASE PLANS EVEN THOUGH |
| THESE SYSTEMS WILL BE UNDER SEPARATE PERMITS AND PLANS |
| AT A LATER DATE. PLEASE SEE THE 2004 FBC 11-4.28.1,.2 |
| AND .3(4) FOR MINIMUM LEVELS TO BE INDICATED. |
| |
| 5) NOTE: PLEASE CLARIFY ELECTRICAL SHUNT FOR ELECTRICAL |
| DEVICES AND/OR EQUIPMENT UNDER HOOD. PLEASE SEE |
| NFPA-96. |
| |
| 6) NOTE: PLEASE PROVIDE LOAD ON THE EXISTING 600AMP |
| MAIN SERVICE WHICH THIS NEW SERVICE IS BEING TAPPED |
| FROM GUTTER. |
| PLEASE INDICATE. 220, 215.5, 220.3, 220.12, |
| 220.14,220.42 220.87 ETC |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 7) NOTE: PLEASE INDICATE A *FLOATING NEUTRAL KIT* |
| REQUIRED AT THE METER CAN. THIS CAN BE DONE BY A NOTE |
| ON PLANS. 250.6, 250.24B. |
| |
| 8) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS FOR |
| SHOW WINDOWS WERE DERIVED. (X-AMOUNT OF FEET TIMES |
| 200VQA PER FT =Y). PLEASE PROVIDE IN THE SUMMARY HOW |
| RECEPTACLE LOAD WAS DERIVED. (X AMOUNT OF DEVICES TIMES |
| 180VA=?). |
| PLEASE CLARIFY WHERE THE CONTINUOUS LOAD WAS DERIVED. |
| THIS CAN BE DONE WITH THE LIGHTING LOADS. |
| 220.43, 220.44 ETC. |
| FBC 106.1.2, 106.3.5.1.2. |
| |
| 9) NOTE: PLEASE CLARIFY CONTROL DEVICES BEING SHOWN FOR |
| HALLWAY/EGRESS LIGHTS AS A S/D. IS THIS A DIMMER? |
| PLEASE CLARIFY HOW THE MINIMUM LIGHTING LEVELS FOR |
| EGRESS UNDER NORMAL CONDITIONS WILL BE MET BY PLACING A |
| DIMMER ON THESE LIGHTS TO MEET LS 101 7.8,7.9. |
| * PLEASE ALSO SEE THESE DEVICE IS LISTED WITH PART OF |
| THE CONTROL DEVICES FOR AUTOMATED SHUT OFF OF LIGHTS. |
| 13-415.1.ABC.1.1, .1.2, .1.3. |
| |
| 10) NOTE: PLEASE SEE ALL SWITCHES ARE BEING SHOWN AS |
| PASSIVE INFRARED FOR LIGHTING CONTROL WHICH IS OK; |
| HOWEVER PLEASE SEE NOTE ABOVE FOR EGRESS AND PLEASE |
| CLARIFY HOW COVERAGE WILL BE MET FOR EGRESS AND NORMAL |
| OPERATION AS MANY OF THE DEVICES ARE BEING LOCATED AT |
| ONE LOCATION ON A WALL IN KITCHEN AREA. PLEASE SEE |
| DEVICES WHICH ARE IN INDIVIDUAL ROOMS LIKE THE |
| BATHROOMS WHICH CONTAIN FLOOR TO CEILING HEIGHT |
| PARTITIONS IS OK, HOWEVER THE COVERAGE FOR OVERRIDING |
| DURING NORMAL BUSINESS HOURS SEEMS LIKE IT WILL NOT |
| PROVIDE THE NEEDED CONTROL FOR LIGHTING AS SHOWN. |
| PLEASE SEE MEANS TO OVER RIDER LIGHTING IS ALSO |
| REQUIRED TO BE AT MEANS OF INGRESS INTO AREA/SPACE. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| PLEASE CALL TO GO OVER SCENARIO AS SHOWN. |
| |
| 10) NOTE: PLEASE SEE THE *OR* OPTION FOR FEEDERS FROM |
| THE METER TO PANEL *A* WHICH IS SHOWING A 1/0 EQUIPMENT |
| GROUNDING CONDUCTOR FOR 400AMPS. THIS IS ONLY BEING |
| NOTED AND DOES NOT CREATE ANY CODE COMMENT. |
| |
| 11) NOTE: PLEASE SEE PLANS MENTIONS EXTERIOR LIGHTING |
| IS BY LANDLORD, IF THIS IS THE CASE PLEASE REMOVE FROM |
| PLANS. PLEASE SEE THE LIGHTING AS SHOWN ON PLANS MAY BE |
| DONE AS PART OF THIS BUILD OUT. |
| PLEASE CLARIFY. |
| FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| |
| 12) NOTE: PLEASE BE SURE TO INCLUDE THE UNIT/SUITE |
| NUMBER ON PLANS FOR LOCATION OF SCOPE OF WORK. THE |
| PERMIT APPLICAITON AND ADDRESS OF SUITE/UNIT APPLIED |
| FOR IN OUR SYSTEM INDICATES SUITE 801. |
| FAC 61G1-16.004 |
| |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |