Plan Review Notes
Plan Review Notes For Permit 07010448
Permit Number 07010448
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-28 18:21:36** UNSAT **
  
 1) NOTE:PLEASE KNOW AS PROJECT WAS APPLIED FOR PERMIT
 AFTER DECEMBER 8TH, 2006 THE FOLLOWING CODES FOR DESIGN
 AND AS REFERENCED ON PLANS HAVE CHANGED.
 PLEASE KNOW THE STATE HAS NOW ADOPTED THE 2006
 REVISIONS TO THE 2004 FBC WHICH HAS CHANGES FOR
 BUILDING, MECHANICAL, PLUMBING AND CHANGES FOR CHAPTER
 13 WHICH WILL AFFECT THE ELECTRICAL PLANS.
 PLEASE ALSO KNOW THE ELECTRICAL CODE NOT ADOPTED AS OF
 12/8/06 IS THE 2005 NFPA-70 (NEC).
 PLEASE BE SURE THE ARCHITECTURAL PLANS AND MEP'S ARE
 UPDATED WITH CODE REFERENCES.
  
 PLEASE ADJUST PLANS, DESIGNS AND PLEASE BE SURE TO SEE
 ANY COMMENTS FROM OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 2) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THE
 PLANS. PLEASE SEE THE CALCULATIONS INDICATE THE
 CONTROLS FOR LIGHTING AS MANUAL.
 PLEASE ALSO PROVIDE PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE VERIFY THE METHOD WHICH IS BEING USED. PLEASE
 SEE THIS IS SUBMITTED AS METHOD *A*WILL THIS
 INCORPORATE ALL AREAS?
 ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT
 SEALED BY THE DESIGNER OF RECORD AS REQUIRED.
 13-103.1.1.1
  
 3) NOTE: PLEASE CORRELATE RISER AND PANEL *A*. PLEASE
 SEE ONE SHOWS 600A MLO AND THE OTHER ON RISER AS 400A
 MLO.
 FBC 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SEE THAT IF ANY FIRE ALARM SYSTEMS ARE
 REQUIRED AND INSTALLED. PLEASE INDICATE ALL THE MINIMUM
 LEVELS FOR THESE DEVICES ON PLANS. PLEASE ALSO INDICATE
 THE LOCATIONS. PLEASE SEE KNOW IF APPLICABLE, THESE
 WILL BE REQUIREDTO BE SHOWN ON BASE PLANS EVEN THOUGH
 THESE SYSTEMS WILL BE UNDER SEPARATE PERMITS AND PLANS
 AT A LATER DATE. PLEASE SEE THE 2004 FBC 11-4.28.1,.2
 AND .3(4) FOR MINIMUM LEVELS TO BE INDICATED.
  
 5) NOTE: PLEASE CLARIFY ELECTRICAL SHUNT FOR ELECTRICAL
 DEVICES AND/OR EQUIPMENT UNDER HOOD. PLEASE SEE
 NFPA-96.
  
 6) NOTE: PLEASE PROVIDE LOAD ON THE EXISTING 600AMP
 MAIN SERVICE WHICH THIS NEW SERVICE IS BEING TAPPED
 FROM GUTTER.
 PLEASE INDICATE. 220, 215.5, 220.3, 220.12,
 220.14,220.42 220.87 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE INDICATE A *FLOATING NEUTRAL KIT*
 REQUIRED AT THE METER CAN. THIS CAN BE DONE BY A NOTE
 ON PLANS. 250.6, 250.24B.
  
 8) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS FOR
 SHOW WINDOWS WERE DERIVED. (X-AMOUNT OF FEET TIMES
 200VQA PER FT =Y). PLEASE PROVIDE IN THE SUMMARY HOW
 RECEPTACLE LOAD WAS DERIVED. (X AMOUNT OF DEVICES TIMES
 180VA=?).
 PLEASE CLARIFY WHERE THE CONTINUOUS LOAD WAS DERIVED.
 THIS CAN BE DONE WITH THE LIGHTING LOADS.
 220.43, 220.44 ETC.
 FBC 106.1.2, 106.3.5.1.2.
  
 9) NOTE: PLEASE CLARIFY CONTROL DEVICES BEING SHOWN FOR
 HALLWAY/EGRESS LIGHTS AS A S/D. IS THIS A DIMMER?
 PLEASE CLARIFY HOW THE MINIMUM LIGHTING LEVELS FOR
 EGRESS UNDER NORMAL CONDITIONS WILL BE MET BY PLACING A
 DIMMER ON THESE LIGHTS TO MEET LS 101 7.8,7.9.
 * PLEASE ALSO SEE THESE DEVICE IS LISTED WITH PART OF
 THE CONTROL DEVICES FOR AUTOMATED SHUT OFF OF LIGHTS.
 13-415.1.ABC.1.1, .1.2, .1.3.
  
 10) NOTE: PLEASE SEE ALL SWITCHES ARE BEING SHOWN AS
 PASSIVE INFRARED FOR LIGHTING CONTROL WHICH IS OK;
 HOWEVER PLEASE SEE NOTE ABOVE FOR EGRESS AND PLEASE
 CLARIFY HOW COVERAGE WILL BE MET FOR EGRESS AND NORMAL
 OPERATION AS MANY OF THE DEVICES ARE BEING LOCATED AT
 ONE LOCATION ON A WALL IN KITCHEN AREA. PLEASE SEE
 DEVICES WHICH ARE IN INDIVIDUAL ROOMS LIKE THE
 BATHROOMS WHICH CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS IS OK, HOWEVER THE COVERAGE FOR OVERRIDING
 DURING NORMAL BUSINESS HOURS SEEMS LIKE IT WILL NOT
 PROVIDE THE NEEDED CONTROL FOR LIGHTING AS SHOWN.
 PLEASE SEE MEANS TO OVER RIDER LIGHTING IS ALSO
 REQUIRED TO BE AT MEANS OF INGRESS INTO AREA/SPACE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
 PLEASE CALL TO GO OVER SCENARIO AS SHOWN.
  
 10) NOTE: PLEASE SEE THE *OR* OPTION FOR FEEDERS FROM
 THE METER TO PANEL *A* WHICH IS SHOWING A 1/0 EQUIPMENT
 GROUNDING CONDUCTOR FOR 400AMPS. THIS IS ONLY BEING
 NOTED AND DOES NOT CREATE ANY CODE COMMENT.
  
 11) NOTE: PLEASE SEE PLANS MENTIONS EXTERIOR LIGHTING
 IS BY LANDLORD, IF THIS IS THE CASE PLEASE REMOVE FROM
 PLANS. PLEASE SEE THE LIGHTING AS SHOWN ON PLANS MAY BE
 DONE AS PART OF THIS BUILD OUT.
 PLEASE CLARIFY.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 12) NOTE: PLEASE BE SURE TO INCLUDE THE UNIT/SUITE
 NUMBER ON PLANS FOR LOCATION OF SCOPE OF WORK. THE
 PERMIT APPLICAITON AND ADDRESS OF SUITE/UNIT APPLIED
 FOR IN OUR SYSTEM INDICATES SUITE 801.
 FAC 61G1-16.004
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]