Plan Review Notes
Plan Review Notes For Permit 07010426
Permit Number 07010426
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-06-12 16:33:11*****DENIED*****
  
  
 1.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL
 BE REFERENCED.
  
 2. THE CORRECT NUMERICAL ADDRESS SHOULD BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.PLANS DO NOT INDICATE IF THE PROPOSED STRUCTURE IS
 ADJOINING OR INDEPENDANT OF AN EXISTING BUILDING.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS RESPONSE TO THE PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS AND ROADS).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW