Plan Review Notes
Plan Review Notes For Permit 07010426
Permit Number 07010426
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-08 11:52:15 
 ** UNSAT **
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC).
  
 2) NOTE: PLEASE SEE RISER NOW INDICATES 2/0 CONDUCTORS
 BEING FED TO A 60A BREAKER. PLEASE KNOW THIS IS NOT
 POSSIBLE AS THIS SIZE CONDUCTOR WILL NOT FIT INTO THE
 LUGS.225.31-225.39 FOR DISCONNECTING MEANS FOR THE
 CIRCUIT(S) TO THIS DETACHED STRUCTURE. PLEASE INDICATE
 WHERE THE FEED IS COMING FROM AND HOW IT IS GETTING TO
 THIS NEW LOCATION.
 PLEASE INDICATE THE SIZE OF THE CIRCUITS, CONDUCTORS
 ETC.
 240.4, 310.16, 408.4, 300.5 ETC
  
 3) NOTE: PLEASE SEE NO PANEL SCHEDULE FOR CIRCUITS AT
 THE DETACHED BUILDING WAS SUBMITTED.
 PLEASE SEE 408.4.
  
 4) NOTE: PLEASE ALSO THE MISSING GROUNDING ELECTRODE
 CONNECTION. PLEASE SEE 250.32 AND 250.50
  
 5) NOTE: PLEASE SEE RISER DOES NOT INDICATE ANY OCP AT
 THE MAIN EXISTING PANEL AS SHOWN TO FEED NEW PANEL.
 PLEASE ALSO CLARIFY WHAT IS BEING SHOWN AS TWO CONDUITS
 FROM THE MAIN EXISTING PANEL TO NEW PANEL.
 FBC 106.1.2, 106.3.5.1.2
 PLEASE SEE 408.4, 240.4, 310.16.
  
 6) NOTE: PLEASE SEE THE ADDRESS FOR SAID PROJECT HAS
 NOW CHANGED, PLEASE BE SURE TO REVISED PERMIT
 APPLICATION AND PLAN TITLE BLOCKS TO NEW ADDRESS.
 FAC 61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  