2007-06-08 11:52:15 | |
| ** UNSAT ** |
| |
| 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| RELEVANT. |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| (NEC). |
| |
| 2) NOTE: PLEASE SEE RISER NOW INDICATES 2/0 CONDUCTORS |
| BEING FED TO A 60A BREAKER. PLEASE KNOW THIS IS NOT |
| POSSIBLE AS THIS SIZE CONDUCTOR WILL NOT FIT INTO THE |
| LUGS.225.31-225.39 FOR DISCONNECTING MEANS FOR THE |
| CIRCUIT(S) TO THIS DETACHED STRUCTURE. PLEASE INDICATE |
| WHERE THE FEED IS COMING FROM AND HOW IT IS GETTING TO |
| THIS NEW LOCATION. |
| PLEASE INDICATE THE SIZE OF THE CIRCUITS, CONDUCTORS |
| ETC. |
| 240.4, 310.16, 408.4, 300.5 ETC |
| |
| 3) NOTE: PLEASE SEE NO PANEL SCHEDULE FOR CIRCUITS AT |
| THE DETACHED BUILDING WAS SUBMITTED. |
| PLEASE SEE 408.4. |
| |
| 4) NOTE: PLEASE ALSO THE MISSING GROUNDING ELECTRODE |
| CONNECTION. PLEASE SEE 250.32 AND 250.50 |
| |
| 5) NOTE: PLEASE SEE RISER DOES NOT INDICATE ANY OCP AT |
| THE MAIN EXISTING PANEL AS SHOWN TO FEED NEW PANEL. |
| PLEASE ALSO CLARIFY WHAT IS BEING SHOWN AS TWO CONDUITS |
| FROM THE MAIN EXISTING PANEL TO NEW PANEL. |
| FBC 106.1.2, 106.3.5.1.2 |
| PLEASE SEE 408.4, 240.4, 310.16. |
| |
| 6) NOTE: PLEASE SEE THE ADDRESS FOR SAID PROJECT HAS |
| NOW CHANGED, PLEASE BE SURE TO REVISED PERMIT |
| APPLICATION AND PLAN TITLE BLOCKS TO NEW ADDRESS. |
| FAC 61G1-16.004 |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |