Plan Review Notes
Plan Review Notes For Permit 07010392
Permit Number 07010392
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-19 09:38:59 
  
 DENIED/INCOMPLETE
  
 1} THE SMOKRE DETECTORS THAT ARE REQUIRED PER 313.1.1
 FBC (RESIDENTIAL) WERE REDLINED ON THE PREVIOUS REVIEW,
 AND THAT WAS NOT CORRECTED ON THE RESUBMITTED PLANS.
 ADD SAME TO PLANS.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE SAME ON PLAN. SEE
 REDLINE SET FROM PREVIOUS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718