Plan Review Notes For Permit 07010350 |
Permit Number |
07010350 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-08 12:41:53 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} INDICATE THE SIZE OF THEGROUNDING CONDUCTOR PER | | 250.122, AND THE NUMBER OF UNGROUNDED CONDUCTORS. | | | | 2} INDICATE HOW THE CONDUI AND JUNCTION BOX IS TO BE | | SUPPORTED PER 300.11. | | | | 3} INDICATE THE SIZE OF THE "PVC" JUNCTION BOX SHOWN ON | | THE PLAN PER 314.16. | | | | 4} THE PRIMMARY PERMIT THAT WAS REFERENCED #06031385, | | WAS ISSUED FOR THE EXACT CHANGE OUT OF TWO ROOFTOP | | UNITS.INDICATE ON A SITE PLAN WHICH UNIT THIS | | APPLICATION IS REFERENCING. | | | | NOTE : THE DISCONNECT MUST NOT INTERFERE WITH THE | | REMOVAL OF SERVICE PANELS. | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|