2007-02-25 08:38:38*** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS. STILL
 NEED UTILITY SIGN OFFS FROM FPU, FPLAND CITY WATER
 UTILITES EVEN THOUGH THIS SCOPE OF WORK IS FOR INTERIOR
 DEMO ONLY.
 IT IS KNOWN THAT THE MAIN FPL FEEDS GOT DIRECTLY TO THE
 2ND FLR/ MEZZ LEVEL. ALL POWER ETC SHALL BE
 DISCONNECTED TO THIS BUILDING.
 IT IS SUGGESTED THAT APPLICATIO IS ALSO MADE FOR
 TEMPORARY ELECTRICAL SERVICE FOR CONTRACTION AS NEW
 ELECTRICLA ROOM LOCATION AND EXISTING WILL NOT BE
 PERMITTED TO CONTAIN POWER. MUST BE FROM FROM A
 TEMPORARY SERIVCE.
  
  