2007-05-24 15:38:07 | *** DENIED *** |
| 1) A/C EQUIPMENT LISTING ON MECHANICAL PLANS A/C #1 IS |
| SHOWING THE WRONG TOTAL AND SENSIBLE BTU'S. AND A/C #2 |
| IS NOT SHOWING ANY TOTAL AND SENSIBLE BTU'S. PLEASE |
| CORRECT BOTH. |
| |
| 2) PLEASE SHOW SEER FOR A/C UNITS IN EQUIPMENT |
| LISTING. |
| |
| 3) PLEASE SUBMIT THE "LONG FORM" SHOWING THE |
| CALCULATIONS FOR THE COOLING LOAD CALCULATIONS OR YOU |
| MAY SUBMIT A MANUAL J CALCULATION, SEE 2004 FBC |
| 13-607.1.ACB.1. |
| |
| 4) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS |
| GRILL UNDER COVERED LOGGIA AS IT MAY NEED AN APPROVED |
| EXHAUST HOOD. |
| |
| 5) MECHANICAL PLANS SECOND FLOOR SHOW NO SUPPLY AIR |
| DUCT GOING TO THE 8X6 SUPPLY GRILL IN HER CLOSET |
| (MASTER SUITE) PLEASE CORRECT. |
| |
| 6) THE 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE |
| NEEDS TO BE 18", SEE 2004 FBC/R M1602.4 (A) AND (C) |
| EXCEPT. |
| |
| *** 2004 FBC/R M1602.4.BALANCED RETURN AIR MAY BE |
| ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| ACHIEVE PROPER RETURN AIR BALANCE. |
| (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| SHALL BE INCLUDED. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |