Plan Review Notes For Permit 07010295
Permit Number 07010295
Review Stop M
Sequence Number 2
Notes
Date Text
2007-05-24 15:38:07*** DENIED ***
 1) A/C EQUIPMENT LISTING ON MECHANICAL PLANS A/C #1 IS
 SHOWING THE WRONG TOTAL AND SENSIBLE BTU'S. AND A/C #2
 IS NOT SHOWING ANY TOTAL AND SENSIBLE BTU'S. PLEASE
 CORRECT BOTH.
  
 2) PLEASE SHOW SEER FOR A/C UNITS IN EQUIPMENT
 LISTING.
  
 3) PLEASE SUBMIT THE "LONG FORM" SHOWING THE
 CALCULATIONS FOR THE COOLING LOAD CALCULATIONS OR YOU
 MAY SUBMIT A MANUAL J CALCULATION, SEE 2004 FBC
 13-607.1.ACB.1.
  
 4) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS
 GRILL UNDER COVERED LOGGIA AS IT MAY NEED AN APPROVED
 EXHAUST HOOD.
  
 5) MECHANICAL PLANS SECOND FLOOR SHOW NO SUPPLY AIR
 DUCT GOING TO THE 8X6 SUPPLY GRILL IN HER CLOSET
 (MASTER SUITE) PLEASE CORRECT.
  
 6) THE 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE
 NEEDS TO BE 18", SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT.
  
 *** 2004 FBC/R M1602.4.BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.