Plan Review Notes For Permit 07010295 |
Permit Number |
07010295 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-07-05 15:52:12 | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) THERE IS CONFLICTING ROOF SHEATHING FASTENING | | REQUIREMENTS SPECIFIED ON THE PLANS. NOTES ON A4.0 AND | | A4.1 HAVE 10D NAILS AT 4" AND 6" OC AND 3" AND 6" OC. | | THE DETAIL A 4.1 HAS 8D RING SHANK NAILS AT 4" AND 6" | | OC. PLEASE CORRECT. | | | | 3) ON THE THE FLAT ROOF MATERIAL PRODUCT APPROVAL FOR | | THE VERANDA, SPECIFY WHICH ONE OF THE APPROVED | | ASSEMBLIES WILL BE INSTALLED. SPECIFY THE FASTENING | | OPTION AND THE DESIGN PRESSURE THAT WILL BE USED. | | PLEASE CIRCLE THE APPROPRIATE ITEMS ON THE NOA. IF | | ENHANCED FASTENING IS REQUIRED TO MEET THE UPLIFT | | PRESSURE REQUIREMENTS FOR ROOF ZONES 2 OR 3, SUBMIT RAS | | 117 CALCULATIONS FOR ENHANCED FASTENING AS ALLOWED BY | | LIMITATION #7 ON THE LAST PAGE OF THE NOA. SEE ITEM # | | 20 FROM THE LAST REVIEW. | | | | 4) SUBMIT THE THE INSTALLATION INSTRUCTIONS FOR THE | | OVERHEAD GARAGE DOOR. THE FL COVERSHEET THAT WAS | | SUBMITTED IS FOR A WAYNE-DALTON CORP. ROLL UP DOOR, | | RATHER THAN A SECTIONAL GARAGE DOOR. | | | | 5) THE PRODUCT APPROVALS SUBMITTED FOR THE 6-PANEL | | METAL DOORS ARE LIMITED TO A HEIGHT OF 6'-8" AND THE | | PLANS SPECIFY 8'-0 DOORS. | | | | 6) ADDRESS COMMENTS FROM OTHER REVIEWERS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|