2007-01-05 16:50:34 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
  
 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), ONE MISSING, SEE REVIEWED PLAN.
  
 4} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 5} AHU #1 AND #2 TOTAL 15K ON THE PANEL SCHEDULE, AND
 ARE LISTED AS 20K IN THE CALCS, PLEASE CORRELATE.
  
 6}PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 110,225 AND 230 CAN BE
 REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.