Plan Review Notes
Plan Review Notes For Permit 07010295
Permit Number 07010295
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-26 14:56:45DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ON SHEET C1 UNDER CODE COMPLIANCE IS SPECIFIED AS
 ASCE 7-45. THE CORRECT EDITION IS 02. PLEASE CORRECT.
  
 4) CORRECT THE TYPO ON C1 FOR THE INTERNAL PRESSURE
 COEFFICIENT. THERE IS AN EQUAL SIGN (=)WHERE THE PLUS
 SIGN (+) SHOULD BE.
  
 5) THE SITE PLAN LOT DIMENSIONS DO NOT CONCUR WITH THE
 SURVEY. PLEASE CORRECT.
  
 6) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM PER FBC CHAPTER 13.
  
 7)SHOW COMPLIANCE WITH FBC R311.5.3.2 FOR WINDERS.
 WINDER TREADS SHALL HAVE A MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM) MEASURED AS ABOVE AT A POINT 12 INCHES
 (305) MM FROM THE SIDE WHERE THE TREADS ARE NARROWER.
 WINDER TREADS SHALL HAVE A MINIMUM TREAD DEPTH OF 6
 INCHES (152 MM) AT ANY POINT. WITHIN ANY FLIGHT OF
 STAIRS, THE GREATEST WINDER TREAD DEPTH AT THE 12 INCH
 (305 MM) WALK LINE SHALL NOT EXCEED THE SMALLEST BY
 MORE THAN 3 / 8 INCH (9.5 MM).
  
 8) SPECIFY THE SIZE OF THE ATTIC ACCESS.R807.1 ATTIC
 ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 9) SECTIONS A/A3.0 AND B/A3.0 DO NOT SPECIFY THE
 REINFORCEMENT BAR SIZES. B/A3.O REFERS TO A SCHEDULE,
 WHICH I COULD NOT LOCATE. PLEASE CORRECT.
  
 10) PLEASE CLARIFY THE FOOTING SIZE FOR COLUMN C6 AT
 THE LOGGIA.
  
 11)THE STEEL PLATE DETAIL ON A3.1 HAS A TYPO FOR THE
 BASE. WHERE 4-3/4" HOLDS IS SPECIFIED IT SHOULD BE
 4-3/4" HOLES.
  
 12) ON A3.1 STANDARDS: ACI 318-99 SHOULD BE THE 2002
 EDITION PER FBC CHAPTER 35.
  
 13) PLEASE CORRECT THE ROOF SHEATHING SCHEDULE ON A4.0.
 THE CORNERS OF HIP ROOFS ARE ZONE 3. SEE FBC FIGURE
 R301.2(8).
  
 14) ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH
 SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGN-WIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. PLEASE REVISE NOTES ON A2.
  
 15) ON A 4.0 TWO SIMPSON FGTR ARE SPECIFIED AT THE WOOD
 COLUMNS. THESE ARE LISTED IN THE SIMPSON CATALOG FOR
 MASONRY OR CONCRETE TO TRUSS APPLICATIONS. SUBMIT
 MANUFACTURER'S SPECIFICATIONS OR PRODUCT APPROVALS
 SPECIFYING WOOD TO TRUSS ATTACHMENT.
  
 16) THE USP HD2 STRAPS HAVE A 1-1/2" WIDTH AT THE TRUSS
 AND DO NOT APPEAR TO BE ABLE TO BE USED WHERE SPECIFIED
 ON A4.0 AND A5.1. PLEASE CLARIFY.
  
 17) ON A/A5.0 PAPER BACK LATH WITH 2 COAT 5/8 " THICK
 STUCCO IS SPECIFIED AT LOGGIA COLUMN. PLEASE CLARIFY.
 ASTM C 926 REQUIRES 3 COATS OF STUCCO 3/4" THICK WHEN
 APPLIED OVER WIRE LATH ON SOLID BACKING.
  
 18) THE 4 X 4 WOOD POST ANCHOR NOTES ON A4.1 AND NOTES
 ON SECTION A/A5.1 APPEAR TO SPECIFY THE TOP AND BOTTOM
 ANCHORS REVERSED. PLEASE CORRECT SO THAT THEY BOTH
 CONCUR.
  
 19) PLEASE SPECIFY THE FASTENING SYSTEM THAT WILL BE
 USED TO ATTACH THE MONIER ROOF TILES. CIRCLE THE
 APPROPRIATE FASTENING SYSTEM ON THE NOA.
  
 20) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF
 MATERIALS THAT WILL BE USED AT THE VERANDA AND THE
 BALCONY. SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES
 WILL BE INSTALLED. SPECIFY THE FASTENING OPTION AND THE
 DESIGN PRESSURE FROM THE PRODUCT APPROVAL. CIRCLE THE
 APPROPRIATE ITEMS. IF ENHANCED FASTENING IS REQUIRED
 FOR THE PERIMETER OR CORNER ZONES TO MEET INCREASED
 UPLIFT IN THOSE AREAS, SUBMIT RAS 117 CALCULATIONS PER
 LIMITATION #7.
  
 21) PLEASE SEPARATE THE DIFFERENT PRODUCT APPROVALS AND
 STAPLE THEM TOGETHER.
  
 22) THE NOA SUBMITTED FOR THE PGT FRENCH DOORS NOA
 02-0701.12 IS EXPIRED. SUBMIT A CURRENT NOA.
  
 23) THE PRODUCT APPROVALS SUBMITTED FOR THE ANDERSON
 SINGLE OUTSWING FRENCH DOOR HAS NOT BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 24) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR 6-PANEL
 METAL DOORS AND THE DOUBLE OUTSWING ENTRY DOORS.
  
 25) PROVIDE A LINTEL SCHEDULE ON THE PLANS.
  
 26) SUBMIT PRODUCT APPROVALS FOR THE LINTELS AND THE
 TRUSS CONNECTORS.
  
 27) REVISE THE APPROVED PRODUCT LIST ON C1 TO INCLUDE
 CORRECTIONS AND NEW ITEMS REQUESTED OR PUT APPROVAL
 STAMP AND INITIALS ON EACH OF THE NOAS.
  
 28) SHOW COMPLIANCE WITH R502.12 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ).
 DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS
 ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING
 MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN
 FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING
 CIRCUMSTANCES:
 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING.
 2.FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE
 OPEN-WEB OR PERFORATED MEMBERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714