Plan Review Notes
Plan Review Notes For Permit 07010055
Permit Number 07010055
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-18 08:45:49 
 ** DENIED REVISION **
  
 1) NOTE: PLEASE SUBMIT REVISED PLANS WHICH ARE DONE BY
 THE DESIGNER/ENGINEER OF RECORD.
 FS 471.025
  
 2) NOTE: PLEASE BE SURE TO CORRELATE THE SWITCH DEVICES
 WITH THE SAME TYPE AS REFERENCED ON ORIGINAL PLANS.
 13-101,13-415.1.ABC.1.1, .1.2.
  
 3) NOTE: PLEASE SEE ORIGINAL PLANS WERE REDLINED FOR
 MINIMUM STROBES LEVELS FOR FBC ADA COMPLIANCE AND NO
 LEVELS ARE STILL INDICATED. PLEASE SEE FBC
 11-4.28.1,.2, AND .3(4).
 THIS WOULD ALSO BE THE SAME SECTIONS FOR HORN DEVICES.
  
 4) NOTE: PLEASE SEE 13-415.2 FOR MAXIMUM LIGHTING
 LEVELS.
  
 5) NOTE: PLEASE CLARIFY WHERE THE EMERGENCY LIGHT
 FIXTURE WHICH WAS ON PREVIOUS PLANS IS?
 PLEASE ALSO SEE PREVIOUS PLANS WERE REDLINED FOR
 CIRCUITING PER 700.12F.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  