Plan Review Notes For Permit 07010055 |
Permit Number |
07010055 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-24 14:09:55 | ******DENIED***** | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. | | | | 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | NEW BUILDING MATERIALS SHALL NOT HINDER OR INTERFERE | | ACCESS TO OR EXIT FROM THE STRUCTURE. | | | | 5.ARE THERE ANY FIRE PROTECTION SYSTEM DEVICE(S) ( | | I.E. SPRINKLER HEADS, EMERGENCY LIGHTS, STROBES, ETC) | | IN THE SCOPE OF WORK AREA?IF THERE ARE, WILL THERE BE | | A NEED FOR THE DEVICE(S) TO BE MODIFIED DUE TO THE | | SCOPE OF WORK?PLEASE BE ADVISED THAT FIRE PROTECTION | | SYSTEMS SHALL BE KEPT IN SERVICE.THE FIRE DEPT. WILL | | BE NOTIFIED IF THE SYSTEM IS SHUT DOWN AND WHEN IT IS | | RETURNED TO SERVICE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|