Date |
Text |
2007-01-14 16:51:00 | |
| ** UNSAT ** |
| |
| 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| RELEVANT. |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| (NEC). |
| |
| |
| 2) NOTE: PLEASE SEE ONE SET OF THE PLANS ARE |
| PHOTO-COPIES OF SIGNED AND SEALED PLANS. |
| PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 WHICH |
| REQUIRES BOTH SETS TO BE SIGNED, DATED AND SEALED AS |
| ORIGINAL. |
| THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| OTHER REVIEWER(S). |
| |
| 3) NOTE: PLEASE SHOW EITHER EXISTING OR NEW TO BE |
| PROVIDED BATTERY BACK UP EMERGENCY LIGHT OF SOME KIND |
| REQUIRED FOR EGRESS. |
| LS 101 7.8, 7.9. |
| NEC 700.16, 700.12E. |
| |
| 4) NOTE: PLEASE KNOW IF THIS BUILDING WHICH MOST LIKELY |
| CONTAINS A FIRE ALARM SYSTEM, SHOULD SHOW NEW OR |
| EXISTING, HORNS, STROBES OR HORN/STROBES WHICH MEET THE |
| MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND 3(4) FOR ADA. |
| THIS SCOPE OF WORK IS CREATING ADA COMPLIANT BATHROOMS, |
| PLEASE SHOW FOR COMPLIANCE. |
| PLEASE SHOW THE DEVICES AND LEVELS. |
| PLEASE KNOW THAT ANY ADDITIONS TO THE FIRE ALARM WILL |
| ALSO BE REQUIRED TO BE UNDER A SEPARATE PERMIT HOWEVER |
| THESE BASE SYSTEM DEVICES ARE REQUIRED AT THIS TIME. |
| FBC 106.3.5.1.2 ADMIN SECTION. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |