Plan Review Notes
Plan Review Notes For Permit 07010055
Permit Number 07010055
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-14 16:51:00 
 ** UNSAT **
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC).
  
  
 2) NOTE: PLEASE SEE ONE SET OF THE PLANS ARE
 PHOTO-COPIES OF SIGNED AND SEALED PLANS.
 PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 WHICH
 REQUIRES BOTH SETS TO BE SIGNED, DATED AND SEALED AS
 ORIGINAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SHOW EITHER EXISTING OR NEW TO BE
 PROVIDED BATTERY BACK UP EMERGENCY LIGHT OF SOME KIND
 REQUIRED FOR EGRESS.
 LS 101 7.8, 7.9.
 NEC 700.16, 700.12E.
  
 4) NOTE: PLEASE KNOW IF THIS BUILDING WHICH MOST LIKELY
 CONTAINS A FIRE ALARM SYSTEM, SHOULD SHOW NEW OR
 EXISTING, HORNS, STROBES OR HORN/STROBES WHICH MEET THE
 MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND 3(4) FOR ADA.
 THIS SCOPE OF WORK IS CREATING ADA COMPLIANT BATHROOMS,
 PLEASE SHOW FOR COMPLIANCE.
 PLEASE SHOW THE DEVICES AND LEVELS.
 PLEASE KNOW THAT ANY ADDITIONS TO THE FIRE ALARM WILL
 ALSO BE REQUIRED TO BE UNDER A SEPARATE PERMIT HOWEVER
 THESE BASE SYSTEM DEVICES ARE REQUIRED AT THIS TIME.
 FBC 106.3.5.1.2 ADMIN SECTION.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved