2007-02-03 16:00:11*****DENIED*****
  
  
  
 1.AS AGREED UPON AT MEETING WITH FIRE MARSHAL MIKE
 CARSILLO ON 02/02/2007, FIRE SPRINKLER HEADS WILL BE
 INSTALLED AT THE TOP AND BOTTOM OF DRYER EXHAUST DUCT.
 MECHANICAL GUARDS WILL BE REQUIRED.DRAWINGS NEED TO
 REFLECT THESE INSTALLATIONS.
  
 2.AS PER FLORIDA STATUTES 471.023 AND FLORIDA
 ADMINISTRATIVE CODES61G15-23.002:THE PRINTED NAME,
 PRINTED PE NUMBER, AND THE CERTIFICATE OF AUTHORIZATION
 NUMBER IS NEEDED ON ALL THE TITLE BLOCKS.
  
  
 PLEASE BE ADVISED THAT ONLY THREE (3) SETS OF PLANS AND
 HYDRAULIC CALCULATIONS WILL BE PROCESSED BY THIS
 OFFICE.
  
  