Plan Review Notes For Permit 07010051 |
Permit Number |
07010051 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-03 16:00:11 | *****DENIED***** | | | | | | | | 1.AS AGREED UPON AT MEETING WITH FIRE MARSHAL MIKE | | CARSILLO ON 02/02/2007, FIRE SPRINKLER HEADS WILL BE | | INSTALLED AT THE TOP AND BOTTOM OF DRYER EXHAUST DUCT. | | MECHANICAL GUARDS WILL BE REQUIRED.DRAWINGS NEED TO | | REFLECT THESE INSTALLATIONS. | | | | 2.AS PER FLORIDA STATUTES 471.023 AND FLORIDA | | ADMINISTRATIVE CODES61G15-23.002:THE PRINTED NAME, | | PRINTED PE NUMBER, AND THE CERTIFICATE OF AUTHORIZATION | | NUMBER IS NEEDED ON ALL THE TITLE BLOCKS. | | | | | | PLEASE BE ADVISED THAT ONLY THREE (3) SETS OF PLANS AND | | HYDRAULIC CALCULATIONS WILL BE PROCESSED BY THIS | | OFFICE. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|