2007-01-02 16:05:24 | INSPECTOR PLEASE NOTE CHANGES IN PIPE SIZES AND NFPA | | ONLINE SIZING TABLES DUE TO THE FACT THE GAS SYSTEM IS | | OVER 200'. | | | | ****************PROVISO**************** | | FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | GEN/RES PERMIT REQUIRED WITH ZONING, ELECTRICAL AND GAS | | APPROVAL OF GENERATOR PLACEMENT. PER FBC-2004 FUEL GAS, | | SECTION 404.12 GAS CONNECTIONS THAT DO NOT CONNECT TO | | APPLIANCES SHALL BE CAPPED GAS TIGHT. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. | | MINIMUM 3,755 CUBIC FEET REQUIRED. | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | |
|