Plan Review Notes
Plan Review Notes For Permit 06120709
Permit Number 06120709
Review Stop P
Sequence Number 2
Notes
Date Text
2007-01-05 15:22:28PASSED/PROVISO
  
 FOUNDATION PERMIT ONLY
  
 1.SECTION 403.1.1 POTTY PARITY HAS NOT BEEN
 ADDRESSED. THIS MAY BE OF SOME CONCERN FOR THE 1ST
 FLOOR TOILET ROOMS IN THE ASSEMBLY OCCUPANCIES. THE
 CONTRACTORS SHALL PROCEED AT THEIR OWN RISK. (SEE
 COMMENT 55B FROM THE BLD-COM PERMIT 06100574).
  
 2. THE STORM PIPING APPEARS TO BE ADEQUATE SIZE PER
 TABLE 1106.3, BUT THE TOTAL SQUARE FOOTAGE HAS NOT BEEN
 VERIFIED AT THIS TIME. THE CONTRACTOR SHALL PROCEED AT
 THEIR OWN RISK.
  
 3. AN APPROVED SANITARY RISER DIAGRAM HAS NOT BEEN
 SUBMITTED FOR THE FOUNDATION WORK AT THIS TIME.
 SANITARY RISER DIAGRAMS REFLECTING THE FLOOR PLAN SHALL
 BE SUBMITTED AND APPROVED FOR THE HORIZONTAL BUILDING
 DRAINSPRIOR TO 1ST INSPECTION OF THE UNDERGROUND
 PIPING. CONTRACTOR SHALL PROCEED AT THEIR OWN RISK.
  
 4. PLEASE SUBMIT THE REQUIRED INFORMATION FOR THE
 UNDERGROUND PIPING BY JANUARY 19, 2007 SO AS NOT TO
 DELAY THE CONSTRUCTION PROCESS.
  