2007-01-04 11:11:08 | *****REDLINED PLANS.******* |
| |
| |
| |
| ** SET OF ELECTRICAL PLANS STMAPED 1/04/07 IS FOR UNDER |
| GROUND INSTALLATIONS OF ELECTRICAL CONDUITS FOR MAIN |
| ELECTRICAL DISTRIBUTION SYSTEM, AND ANY STUB UP |
| LOCATIONS FOR FUTURE BRANCH CIRCUIT POWER/LIGHTING AND |
| LOW VOLTAGE LOCATIONS. |
| |
| ** SHEETS REDLINED FOR ATTACHMENTAND INSTALLATION OF |
| ALLGROUNDING ELECTRODE SYSTEM CONDUCTORS FOR THE MAIN |
| SYSTEM AND STUB UPS FOR FUTURE GROUNDING ELECTRIDE |
| RISER. THIS IS INCLUSIVE OF THE UNDERGROUND SLAB |
| ATTACHMENTS FOR THE LIGHTNING PROTECTIONSYSTEM |
| UNDERGROUNDS. DETAILS AND NOTES ARE ON PLANS. |
| |
| ** SHEETS ALSO INCLUDE INSTALLATION OF MANHOLES AND |
| DUCT BANKS TO EACH SECTION OF OF THE SITE. |
| |
| ELECTRICAL CONTRACTOR(S)/ CERTIFIED LIGHTNING |
| PROTECTION INSTALLATION CONTRACTOR(S)FOR SCOPE OF |
| WORK FOR MAIN ELECTRICAL SYSTEM AND ANY LIGHTNING |
| PROTECTION MAY REFERENCE THESE PLANS AND PERMIT NUMBER |
| FOR THEIR SCOPE OF WORK. LIGHTING PROTECTION WORK FOR |
| FOUNDATION WILL BE A SEPARATE ELECTRICAL PERMIT FROM |
| THE MAIN ELECTRICAL UNDERGROUND SCOPE. |
| |
| THIS PERMITTED SET OF PLANS FOR FOUNDATION DOES NOT |
| INCLUDE ANY REVIEWS FOR THE BUILDING MAIN ELECTRICAL |
| SYSTEM, ONLY THAT FOR CONDUIT SIZES AND NOTES ABOVE. |
| |
| ALL THREE SETS STAMPED |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2007-01-04 06:54:22 | 2007-01-04 06:54:22 |
| IN ELEC FOR REVIEW |