Plan Review Notes
Plan Review Notes For Permit 06120709
Permit Number 06120709
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-29 15:22:54*** UNSAT ***
  
  
 CITY CENTER FOUNDATION PERMIT APPLICATION REVIEW
 PERMIT # 06120709
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED PLANS FOR REVIEW DID
 NOT CONTAIN ANY OF THE ELECTRICAL SHEETS REQUIRED FOR
 INFORMATION ON THE BUILDINGS GROUNDING ELECTRODE SYSTEM
 AND LIGHTNING PROTECTION GROUNDING AS REQUIREDPER
 250.50, 250.52, 250.54, 250.58, 250.104, 250.106 ETC
 WHICH WERE ALL A PART OF THE MAIN BUILDING ELECTRICAL
 SET OF PLANS. THESE ITEMS WHICH ARE REQUIRED AND WILL
 BE PART OF THE FOUNDATION OF BUILDING ARE REQUIRED TO
 BE SUBMITTED AS PART OF THIS PERMIT PACKAGE AND PERMIT
 FOR REVIEW.
 FBC ADMINISTRATIVE SECTIONS 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THAT THE SUBMITTED PLANS DO NOT
 CONTAIN ALL INFORMATION AS NEEDED FOR THE UNDER
 ELECTRICAL CONDUITS WHICH WILL BE PART OF THE
 FOUNDATION/SLAB WORK. PLEASE SEE MISSING SHEETS FROM
 MAIN PLANS OR SHEETS WHICH MAY BE CREATED FOR
 SLAB/FOUNDATION WHICH INDICATE THE CONDUIT SIZES WHICH
 WILL BE INSTALLED FOR ALL ELECTRICAL LOCATIONS WHICH
 ARE PART PF THE FOUNDATION.
 IE; FIRE PUMP, MAIN SWITCH GEAR, 1HMGA, 1HMGB,AND ANY
 OTHER MAIN ELECTRICAL EQUIPMENT PANEL LOCATIONS WHICH
 WILL BE FED FROM UNDERGROUND CONDUITS ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE SEE MAIN PLANS FOR LIGHTNING PROTECTION
 SYSTEM(S) WHICH IS PART OF THE FOUNDATION WORK.
 250.106, NFPA-780
  
 4) NOTE: PLEASE SEE 314 PART IV SECTIONS 314.50-314.59
 FOR THE MANHOLES WHICH WILL BE PART OF THE FOUNDATION.
 PLEASE INDICATE SIZES, CONSTRUCTION ETC. PLEASE KNOW
 THIS IS ONE ITEM WHICH COLD BE REDLINED, HOWEVER THIS
 INFORMATION WOULD BE REQUIRED BEFORE ANY CONCRETE WOULD
 BE POURED FOR THESE AREAS, INCLUDING PULL BOXES AS
 SHOWN ON PLANS BETWEEN GARAGE AND CITY HALL SECTION.
 PREVIOUS REVIEW NOTES.
  
 5) NOTE: PLEASE SEE THE SUBMITTED PLANS INCLUDE ALL
 FIRST FLOOR LEVEL FIRE SPRINKLER LINES WHICH WILL BE
 REVIEWED BY THE MARSHAL?S OFFICE, CHIEF MIKE CARSILLO.
  
  
 6) NOTE: PLEASE SEE AS REVIEWING PLANS SUBMITTED THE
 "S" SHEETS ARE MISSING THE TITLE BLOCKS AS REQUIRED PER
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002. PLEASE SEE
 THE SHEETS NOW CONTAIN THE CERTIFICATE OF AUTHORIZATION
 NUMBER WHICH IS OK AND HAS BEEN VERIFIED WITH THE STATE
 OF FLORIDA.THIS INFORMATION MAY BE PLACED ON SHEETS
 IN ALL THREE SETS PENDING STRUCTURAL REVIEW.THE
 COMPLETED TITLE BLOCK INFORMATION MAY BE DONE BY A
 STAMP, LABEL, OR HAND WRITTEN IF SO CHOSEN.
  
  
  
 ** ONE ROLL OF PLANS SENT TO FIRE AND TWO OTHER ROLLS
 WILL BE PLACED ON JIM WITMER'S DESK FOR BUILDING AND
 OTHER REVIEWS TO TAKE PLACE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717