2006-12-29 15:22:54 | *** UNSAT *** |
| |
| |
| CITY CENTER FOUNDATION PERMIT APPLICATION REVIEW |
| PERMIT # 06120709 |
| |
| |
| 1) NOTE: PLEASE SEE THE SUBMITTED PLANS FOR REVIEW DID |
| NOT CONTAIN ANY OF THE ELECTRICAL SHEETS REQUIRED FOR |
| INFORMATION ON THE BUILDINGS GROUNDING ELECTRODE SYSTEM |
| AND LIGHTNING PROTECTION GROUNDING AS REQUIREDPER |
| 250.50, 250.52, 250.54, 250.58, 250.104, 250.106 ETC |
| WHICH WERE ALL A PART OF THE MAIN BUILDING ELECTRICAL |
| SET OF PLANS. THESE ITEMS WHICH ARE REQUIRED AND WILL |
| BE PART OF THE FOUNDATION OF BUILDING ARE REQUIRED TO |
| BE SUBMITTED AS PART OF THIS PERMIT PACKAGE AND PERMIT |
| FOR REVIEW. |
| FBC ADMINISTRATIVE SECTIONS 106.1.2, 106.3.5.1.2 |
| |
| 2) NOTE: PLEASE SEE THAT THE SUBMITTED PLANS DO NOT |
| CONTAIN ALL INFORMATION AS NEEDED FOR THE UNDER |
| ELECTRICAL CONDUITS WHICH WILL BE PART OF THE |
| FOUNDATION/SLAB WORK. PLEASE SEE MISSING SHEETS FROM |
| MAIN PLANS OR SHEETS WHICH MAY BE CREATED FOR |
| SLAB/FOUNDATION WHICH INDICATE THE CONDUIT SIZES WHICH |
| WILL BE INSTALLED FOR ALL ELECTRICAL LOCATIONS WHICH |
| ARE PART PF THE FOUNDATION. |
| IE; FIRE PUMP, MAIN SWITCH GEAR, 1HMGA, 1HMGB,AND ANY |
| OTHER MAIN ELECTRICAL EQUIPMENT PANEL LOCATIONS WHICH |
| WILL BE FED FROM UNDERGROUND CONDUITS ETC. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 3) NOTE: PLEASE SEE MAIN PLANS FOR LIGHTNING PROTECTION |
| SYSTEM(S) WHICH IS PART OF THE FOUNDATION WORK. |
| 250.106, NFPA-780 |
| |
| 4) NOTE: PLEASE SEE 314 PART IV SECTIONS 314.50-314.59 |
| FOR THE MANHOLES WHICH WILL BE PART OF THE FOUNDATION. |
| PLEASE INDICATE SIZES, CONSTRUCTION ETC. PLEASE KNOW |
| THIS IS ONE ITEM WHICH COLD BE REDLINED, HOWEVER THIS |
| INFORMATION WOULD BE REQUIRED BEFORE ANY CONCRETE WOULD |
| BE POURED FOR THESE AREAS, INCLUDING PULL BOXES AS |
| SHOWN ON PLANS BETWEEN GARAGE AND CITY HALL SECTION. |
| PREVIOUS REVIEW NOTES. |
| |
| 5) NOTE: PLEASE SEE THE SUBMITTED PLANS INCLUDE ALL |
| FIRST FLOOR LEVEL FIRE SPRINKLER LINES WHICH WILL BE |
| REVIEWED BY THE MARSHAL?S OFFICE, CHIEF MIKE CARSILLO. |
| |
| |
| 6) NOTE: PLEASE SEE AS REVIEWING PLANS SUBMITTED THE |
| "S" SHEETS ARE MISSING THE TITLE BLOCKS AS REQUIRED PER |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.002. PLEASE SEE |
| THE SHEETS NOW CONTAIN THE CERTIFICATE OF AUTHORIZATION |
| NUMBER WHICH IS OK AND HAS BEEN VERIFIED WITH THE STATE |
| OF FLORIDA.THIS INFORMATION MAY BE PLACED ON SHEETS |
| IN ALL THREE SETS PENDING STRUCTURAL REVIEW.THE |
| COMPLETED TITLE BLOCK INFORMATION MAY BE DONE BY A |
| STAMP, LABEL, OR HAND WRITTEN IF SO CHOSEN. |
| |
| |
| |
| ** ONE ROLL OF PLANS SENT TO FIRE AND TWO OTHER ROLLS |
| WILL BE PLACED ON JIM WITMER'S DESK FOR BUILDING AND |
| OTHER REVIEWS TO TAKE PLACE. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |