Plan Review Notes
Plan Review Notes For Permit 06120684
Permit Number 06120684
Review Stop B
Sequence Number 3
Notes
Date Text
2007-04-09 14:43:20DENIED BY BUILDING
  
 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. SEE FBC CHAPTER 13.
  
 2) THERE ARE TWO COLUMNS SPECIFIED ON SHEET A2 OF THE
 PLANS. ONE IS ALUMINUM AND THE OTHER IS STEEL. SPECIFY
 WHICH ONE WILL BE USED AT THE FRONT ENTRY AND REMOVE
 THE OTHER FROM THE PLANS.
  
 3)PROVIDE A DETAIL OF THE ALUMINUM COLUMN CAP ON THE
 THE ALUMINUM COLUMN AT THE ENTRY PORCH. SPECIFY
 THICKNESS, WELDS, DIMENSIONS , UPLIFT CAPACITY, ETC.
 SEE ITEM #11 FROM FIRST REVIEW. SEE ITEM 12 OF PREVIOUS
 REVIEW.
  
 4) SPECIFY THE REQUIRED DEPTH OF EMBEDMENT INTO THE
 CONCRETE FOOTING FOR THE ALUMINUM COLUMN ON SHEET A2.
 SEE ITEM 13 OF PREVIOUS REVIEW.
  
 5)THE TRUSS LAYOUT WAS NOT SUBMITTED. IN ADDITION TO
 THE RAISED SEAL THE TRUSS DRAWINGS ARE REQUIRED TO HAVE
 THE ORIGINAL WET SIGNATURE OF THE TRUSS ENGINEER. THE
 DRAWINGS THAT WERE SUBMITTED HAVE A SIGNATURE STAMP.
 SEE FS 471. TRUSS LAYOUT AND DRAWINGS FOR CAN BE GIVEN
 TO FIELD INSPECTOR.
  
 6) THE TRUSS LAYOUT AND PRODUCT APPROVALS ARE REQUIRED
 TO BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD FOR THE STRUCTURE. THE DOR FOR THIS PROJECT
 IS AN ENGINEER. THE ENGINEER'S SHOP DRAWING REVIEW
 STAMP WITH THE REVIEW STATUS INDICATED IS REQUIRED ON
 THE THESE ITEMS ALONG WITH HIS SIGNATURE.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR OUTSWING
 FRENCH DOOR SHOWN ON THE PLANS AT THE NEW BATHROOM. SEE
 ITEM #19 FROM THE PREVIOUS REVIEW.
  
 8) SUBMIT PRODUCT APPROVALS FOR STORM PANELS AT THE
 FRENCH DOOR IF IT IS NOT IMPACT RESISTANT.
  
 9) SPECIFY THE THE FASTENING OPTION THAT WILL BE USED
 TO INSTALL THE ASSEMBLY THAT WAS SELECTED ON PAGE 16 OF
 THE NOA FOR THE TAMKO MODIFIED ROOFING SYSTEM. SUBMIT
 THE RAS 117 CALCULATIONS FOR THE ENHANCED FASTENING
 THAT WILL BE REQUIRED AT EDGES AND CORNERS. SEE # 21 ON
 PREVIOUS REVIEW.
  
 10) THE INFORMATION SUBMITTED FOR THE TRUSS CONNECTORS
 AND LINTELS ARE NOT THE PRODUCT APPROVALS. PRODUCT
 APPROVALS CAN BE DOWN LOADED FROM THE INTERNET AT
 WWW.FLORIDABUILDING.ORG.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  