Notes
Date Text
2007-03-20 08:59:30DENIED BY BUILDING
  
 1) THE NOC HAS EXPIRED BECAUSE WORK WAS NOT STARTED
 WITHIN 90 DAYS OF IT BEING RECORDED. THE NOC WILL HAVE
 TO BE RE-RECORDED.
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT
 FEES. NOTE: BE SURE TO RESUBMIT THE OLD PLAN SHEETS
 THAT HAVE THE COUNTY IMPACT FEE STAMPS ON THEM WHEN
 THOSE SHEETS ARE REVISED.
  
 3) SUBMIT A SIGNED AND SEALED SUBSURFACE SOIL REPORT
 FROM A FLORIDA LICENSED SOILS ENGINEER. SEE ITEM 3 OF
 1ST REVIEW.
  
 4) SPECIFY THE TRUSS BOTTOM CORD LIVE LOAD ON SHEET A1.
 SEE FBC TABLE 1607.1.
  
 5) ON SHEET A1 THE ROOF LIVE LOAD IS SPECIFIED AS 30
 PSF IN ONE PLACE AND 10 PSF IN ANOTHER. PLEASE
 CORRECT.
  
 6) ON SHEET A1 THE ROOF DEAD LOAD IS SPECIFIED AS 15
 PSF IN ONE PLACE AND 20 PSF IN ANOTHER. PLEASE
 CORRECT.
  
 7) ON SHEET A1 THE ROOF SLOPE SHOULD READ GREATER THAN
 10 DEGREES AND LESS THAN 30 DEGREES. PLEASE CORRECT.
  
 8) ON SHEET A1 THE CODE SECTIONS SPECIFIED FOR THE
 EMERGENCY EGRESS WINDOWS ARE INCORRECT. THEY HAVE BEEN
 CHANGED IN THE 2004 FBC. PLEASE CORRECT.
  
 9) THE WORD WIDTH HAS BEEN OMITTED FOR THE 20"
 DIMENSION REQUIREMENT FOR EGRESS OPENINGS.
  
 10) ON A1 THE EGRESS NOTES INCORRECTLY SPECIFY THE
 MINIMUM TOTAL GLASS AREA. THIS SHOULD BE TOTAL NET
 CLEAR OPENING AREA. PLEASE CORRECT.
  
 11)ON A1 THE FLOOR LIVE LOADS ARE INCORRECTLY
 SPECIFIED AS 10 PSF. THE CORRECT FLOOR LIVE LOADS ARE
 30 PSF FOR SLEEPING ROOMS AND 40 PSF FOR OTHER AREAS.
  
 12) PROVIDE A DETAIL OF THE ALUMINUM COLUMN CAP ON THE
 THE ALUMINUM COLUMN AT THE ENTRY PORCH. SPECIFY
 THICKNESS, WELDS, DIMENSIONS , UPLIFT CAPACITY, ETC.
 SEE ITEM #11 FROM FIRST REVIEW.
  
 13) SPECIFY THE REQUIRED DEPTH OF EMBEDMENT INTO THE
 CONCRETE FOOTING FOR THE ALUMINUM COLUMN ON SHEET A2.
  
 14) A STEEL COLUMN FOOTING DETAIL IS SHOWN ON SHEET A1.
 PLEASE CLARIFY WHERE THIS STEEL COLUMN WILL BE
 INSTALLED.
  
 15) THE TRUSS DRAWINGS REFERENCE THE 2001 FBC. PLEASE
 CORRECT TO REFERENCE THE 2004 FBC.
  
 16) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED
 TO REVIEW AND APPROVE THE TRUSS LAYOUT AND DRAWINGS IN
 WRITING.
  
 17) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR
 THE 2 X 12BEAM AT THE ENTRY TO THE STRUCTURE.
  
 18) THE UPLIFT FOR THE SIMPSON MTSM 20 CONNECTORS IS
 SPECIFIED AS 1490. THE SIMPSON CATALOG SPECIFIES 1175.
 PLEASE CORRECT.
  
 19) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR OUTSWING
 FRENCH DOOR.
  
 20) SUBMIT PRODUCT APPROVALS FOR STORM PANELS IF
 GLAZING IS NOT IMPACT RESISTANT.
  
 21) INDICATE WHICH ONE OF THE APPROVED ASSEMBLIES FROM
 THE TAMKO MODIFIED ROOF SYSTEM NOA WILL BE INSTALLED.
 SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE THAT
 WILL BE USED TO INSTALL THE ASSEMBLY. CIRCLE THE
 APPROPRIATE ITEMS ON THE NOA. IF ENHANCED FASTENER
 SPACING IS REQUIRED TO INCREASE THE UPLIFT PRESSURES IN
 ROOF ZONES 2 AND 3, SUBMIT RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON PAGE 19 OF THE
 NOA.
  
 NOTE: SEE RED MARKS AND NOTATIONS ONTHE PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  