2007-03-20 08:59:30 | DENIED BY BUILDING |
| |
| 1) THE NOC HAS EXPIRED BECAUSE WORK WAS NOT STARTED |
| WITHIN 90 DAYS OF IT BEING RECORDED. THE NOC WILL HAVE |
| TO BE RE-RECORDED. |
| |
| 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT |
| FEES. NOTE: BE SURE TO RESUBMIT THE OLD PLAN SHEETS |
| THAT HAVE THE COUNTY IMPACT FEE STAMPS ON THEM WHEN |
| THOSE SHEETS ARE REVISED. |
| |
| 3) SUBMIT A SIGNED AND SEALED SUBSURFACE SOIL REPORT |
| FROM A FLORIDA LICENSED SOILS ENGINEER. SEE ITEM 3 OF |
| 1ST REVIEW. |
| |
| 4) SPECIFY THE TRUSS BOTTOM CORD LIVE LOAD ON SHEET A1. |
| SEE FBC TABLE 1607.1. |
| |
| 5) ON SHEET A1 THE ROOF LIVE LOAD IS SPECIFIED AS 30 |
| PSF IN ONE PLACE AND 10 PSF IN ANOTHER. PLEASE |
| CORRECT. |
| |
| 6) ON SHEET A1 THE ROOF DEAD LOAD IS SPECIFIED AS 15 |
| PSF IN ONE PLACE AND 20 PSF IN ANOTHER. PLEASE |
| CORRECT. |
| |
| 7) ON SHEET A1 THE ROOF SLOPE SHOULD READ GREATER THAN |
| 10 DEGREES AND LESS THAN 30 DEGREES. PLEASE CORRECT. |
| |
| 8) ON SHEET A1 THE CODE SECTIONS SPECIFIED FOR THE |
| EMERGENCY EGRESS WINDOWS ARE INCORRECT. THEY HAVE BEEN |
| CHANGED IN THE 2004 FBC. PLEASE CORRECT. |
| |
| 9) THE WORD WIDTH HAS BEEN OMITTED FOR THE 20" |
| DIMENSION REQUIREMENT FOR EGRESS OPENINGS. |
| |
| 10) ON A1 THE EGRESS NOTES INCORRECTLY SPECIFY THE |
| MINIMUM TOTAL GLASS AREA. THIS SHOULD BE TOTAL NET |
| CLEAR OPENING AREA. PLEASE CORRECT. |
| |
| 11)ON A1 THE FLOOR LIVE LOADS ARE INCORRECTLY |
| SPECIFIED AS 10 PSF. THE CORRECT FLOOR LIVE LOADS ARE |
| 30 PSF FOR SLEEPING ROOMS AND 40 PSF FOR OTHER AREAS. |
| |
| 12) PROVIDE A DETAIL OF THE ALUMINUM COLUMN CAP ON THE |
| THE ALUMINUM COLUMN AT THE ENTRY PORCH. SPECIFY |
| THICKNESS, WELDS, DIMENSIONS , UPLIFT CAPACITY, ETC. |
| SEE ITEM #11 FROM FIRST REVIEW. |
| |
| 13) SPECIFY THE REQUIRED DEPTH OF EMBEDMENT INTO THE |
| CONCRETE FOOTING FOR THE ALUMINUM COLUMN ON SHEET A2. |
| |
| 14) A STEEL COLUMN FOOTING DETAIL IS SHOWN ON SHEET A1. |
| PLEASE CLARIFY WHERE THIS STEEL COLUMN WILL BE |
| INSTALLED. |
| |
| 15) THE TRUSS DRAWINGS REFERENCE THE 2001 FBC. PLEASE |
| CORRECT TO REFERENCE THE 2004 FBC. |
| |
| 16) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED |
| TO REVIEW AND APPROVE THE TRUSS LAYOUT AND DRAWINGS IN |
| WRITING. |
| |
| 17) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR |
| THE 2 X 12BEAM AT THE ENTRY TO THE STRUCTURE. |
| |
| 18) THE UPLIFT FOR THE SIMPSON MTSM 20 CONNECTORS IS |
| SPECIFIED AS 1490. THE SIMPSON CATALOG SPECIFIES 1175. |
| PLEASE CORRECT. |
| |
| 19) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR OUTSWING |
| FRENCH DOOR. |
| |
| 20) SUBMIT PRODUCT APPROVALS FOR STORM PANELS IF |
| GLAZING IS NOT IMPACT RESISTANT. |
| |
| 21) INDICATE WHICH ONE OF THE APPROVED ASSEMBLIES FROM |
| THE TAMKO MODIFIED ROOF SYSTEM NOA WILL BE INSTALLED. |
| SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE THAT |
| WILL BE USED TO INSTALL THE ASSEMBLY. CIRCLE THE |
| APPROPRIATE ITEMS ON THE NOA. IF ENHANCED FASTENER |
| SPACING IS REQUIRED TO INCREASE THE UPLIFT PRESSURES IN |
| ROOF ZONES 2 AND 3, SUBMIT RAS 117 CALCULATIONS AS |
| REQUIRED BY GENERAL LIMITATION #7 ON PAGE 19 OF THE |
| NOA. |
| |
| NOTE: SEE RED MARKS AND NOTATIONS ONTHE PLAN. |
| |