Date |
Text |
2007-01-17 11:29:56 | DENIED |
| REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1 |
| CITY OF WEST PALM BEACH AMENDMENTS |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SHEET A1 SANITARY RISER DIAGRAM: |
| A} SANITARY ISOMETRIC RISER DIAGRAM DOES NOT RELECT THE |
| FLOOR PLAN AND IS NOT CODE COMPLIANT PER FBC-2004 |
| PLUMBING, SECTION 901.2.1 AND FBC-2004 CHAPTER 1, |
| SECTION 106.1.1. PLEASE REFERENCE THE ATTACHED SANITARY |
| RISER DIAGRAM TO THE PLUMBING COMMENTS REFLECTING THE |
| FLOOR PLAN THAT IS CODE COMPLIANT FOR THE RESUBMITTAL. |
| B} PLEASE DELETE THE TRAP INDICATED FOR THE WATER |
| CLOSETS, PER FBC-2004 PLUMBING, SECTION 1002.1 FIXTURES |
| SHALL NOT BE DOUBLE TRAPPED. WATER CLOSETS HAVE AN |
| INTREGRAL TRAP AND DO NOT REQUIRE A TRAP. PLEASE |
| CORRECT AND RESUBMIT. |
| |
| 2. SHEET A1 PLUMBING NOTES: ON NOTE NUMBER ONE PLEASE |
| DELETE 1/8" PER FOOT AND ADD PER FBC-2004, TABLE 704.1. |
| PLEASE CORRECT AND RESUBMIT. |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL AND PLEASE REFERENCE THE ATTACHED SANITARY |
| RISER DIAGRAM TO THE PLUMBING COMMENTS. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |