Plan Review Notes
Plan Review Notes For Permit 06120684
Permit Number 06120684
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-17 11:29:56DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
 CITY OF WEST PALM BEACH AMENDMENTS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A1 SANITARY RISER DIAGRAM:
 A} SANITARY ISOMETRIC RISER DIAGRAM DOES NOT RELECT THE
 FLOOR PLAN AND IS NOT CODE COMPLIANT PER FBC-2004
 PLUMBING, SECTION 901.2.1 AND FBC-2004 CHAPTER 1,
 SECTION 106.1.1. PLEASE REFERENCE THE ATTACHED SANITARY
 RISER DIAGRAM TO THE PLUMBING COMMENTS REFLECTING THE
 FLOOR PLAN THAT IS CODE COMPLIANT FOR THE RESUBMITTAL.
 B} PLEASE DELETE THE TRAP INDICATED FOR THE WATER
 CLOSETS, PER FBC-2004 PLUMBING, SECTION 1002.1 FIXTURES
 SHALL NOT BE DOUBLE TRAPPED. WATER CLOSETS HAVE AN
 INTREGRAL TRAP AND DO NOT REQUIRE A TRAP. PLEASE
 CORRECT AND RESUBMIT.
  
 2. SHEET A1 PLUMBING NOTES: ON NOTE NUMBER ONE PLEASE
 DELETE 1/8" PER FOOT AND ADD PER FBC-2004, TABLE 704.1.
 PLEASE CORRECT AND RESUBMIT.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL AND PLEASE REFERENCE THE ATTACHED SANITARY
 RISER DIAGRAM TO THE PLUMBING COMMENTS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved