2007-01-20 07:49:37DENIED;
 1.FBC-2004 PLUMBING TABLE 403.1 (8S) ONE SEVICE SINK IS
 REQUIRED. LOCATION OF DRINKING FOUNTAIN IS NOT SHOWN.
 ALSO SHOW DRINKING FOUNTAIN ELEVATION ON PAGE A3.01 AND
 FIXTURE SCHEDULE PAGE P001.
 2. LIST MATERIAL TO BE STORED TO DETERMINE IF A
 EMERGENCY SHOWER AND EYEWASH STATION IS REQUIRED.
 3.PAGE P001 PLUMBING FIXTURE SCHEDULE LISTS BATHROOM #
 106 NOT SHOWN ON PLANS, SHOW LOCATION.
 4. CONDENSATE PIPE TO BE SUPPORTED EVERY 4' IF PVC OR
 EVERY 10' IF COPPER, PER TABLE 308.5 ADD NOTE TO PLAN
 AND SPEC OUT MATERIAL TO BE USED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695