Plan Review Notes
Plan Review Notes For Permit 06120663
Permit Number 06120663
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-16 12:24:21*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) SEE PAGE M101 EF-1, SEE HIGH LIGHTED 4_ M701 AND
 HIGH LIGHTED EXISTING O/A, PLEASE REMOVE THESE
 NOTATIONS AS THIS IS AN EXHAUST FAN.
  
 3) SEE PAGE M101, ALL RETURN AIR GRILLS NOTEDAA/-,
 CAN NOT DETERMINE SIZE, PLEASE CORRECT.
  
 4) SEE PAGE M801 EQUIPMENT SCHEDULE, CONDENSER UNIT,
 RATING EER, DO YOU MEAN SEER, IF SO PLEASE CORRECT.
  
 5) SHOW MODEL NUMBERS FOR ALL AHU'S AND CONDENSER UNITS
 IN EQUIPMENT SCHEDULE.
  
 6) A FIRE DAMPER IS REQUIRED AT 8" SUPPLY DUCT
 PENETRATING FIRE RATED WALL IN CORRIDOR, PER 2004 FBC/M
 607.5.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.