Plan Review Notes For Permit 06120663 |
Permit Number |
06120663 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-30 11:16:40 | ***DENIED*** | | | | 1) NFPA 101, AND NFPA 1, 2003 EDITION SHALL BE | | REFERENCED. PLEASE CORRECT ON SHEET A0.02. | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY | | WITH NFPA 241. | | | | 3) ALL NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR | | CLOSURE IN ACCORDANCE WITH UL REQUIREMENTS. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODEL. | | | | 5) ADDRESS SUITE NUMBER TO BE DISPLAYED AT FRONT DOOR | | ENTRANCE, AND BACK ENTRANCE WHERE APPLICABLE. SUITE | | NUMBERS SHALL BE AT LEAST 3" IN HEIGHT AND CONTRASTNG | | TO THE BACKGROUND. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | (561) 805-6722 OR 804-4756 |
|