2007-01-30 11:16:40***DENIED***
  
 1) NFPA 101, AND NFPA 1, 2003 EDITION SHALL BE
 REFERENCED. PLEASE CORRECT ON SHEET A0.02.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
 3) ALL NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR
 CLOSURE IN ACCORDANCE WITH UL REQUIREMENTS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 5) ADDRESS SUITE NUMBER TO BE DISPLAYED AT FRONT DOOR
 ENTRANCE, AND BACK ENTRANCE WHERE APPLICABLE. SUITE
 NUMBERS SHALL BE AT LEAST 3" IN HEIGHT AND CONTRASTNG
 TO THE BACKGROUND.
  
  