Plan Review Notes
Plan Review Notes For Permit 06120663
Permit Number 06120663
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-14 18:04:29** UNSAT **
  
 1) NOTE: PLEASE SEE THE PLANS SHALL STATE THE INTENDED
 OCCUPANCY AND TENANT MATERIALS.
 PLEASE SEE THE DELIVERY AREA STATES A CHAINS LINK FENCE
 FOR WHAT SEEMS LIKE IT SHOULD BE A TENANT SEPARATION?
 PLEASE KNOW THIS INFORMATION IN QUESTION HAS BEEN
 FORWARDED TO THE PLAN REVIEW STAFF WHICH WAS PART OF
 THE PREVIOUS PROJECT FOR THE ADJACENT BUILD OUT.
 TENANT SEPARATION?
 PLEASE KNOW THAT DUE TO THIS INFORMATION NOT STATED ON
 PLANS, SOME ITEMS FOR CODE COMPLIANCE REVIEW CAN NOT BE
 DONE AT THIS TIME.
 NEC 500.
  
 2) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC).
 PLEASE SEE THE OTHER CODES WHICH ARE STATED ON PLANS
 FOR ELECTRICAL SHEETS WHICH ARE ALREADY STATED ARE:
 2002 NFPA-72 AND 2003 NFPA-101.
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER
 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2.
 THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE
 DESIGNER OF RECORD.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES
 TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION
 ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE
 PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS.
 PLEASE SEE THE METHOD B SUBMITTED DOES NOT INDICATE
 AUTOMATED CONTROLS ETC.
 PLEASE SEE LIGHTING DENSITIES.
 PLEASE CLARIFY HOW FINE STORAGE IS DETERMINED. THIS
 SHALL BE REVIEWED BY THIS OFFICE FOR FINAL
 DETERMINATION FOR LIGHTING ALLOWANCE.
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR LIGHTING
 ALLOWANCE AND SHOW COMPLIANCE.
 NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS
 PROVIDED.
  
 4) NOTE: PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS,
 SCHEDULING, DEVICES AND TYPES OF DEVICES.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR
 TIMER TYPE.
 PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE
 EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS,
 HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE
 JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE
 LOAD SIDE OF THESE DEVICES.
 PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW,
 A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
 5) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR THE EGRESS
 AREAS TO THE PUBLIC RIGHT OF WAY INCLUDING STAIRS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
  
 6) NOTE: PLEASE COMPLETE SERVICE RISER DIAGRAM WITH THE
 FOLLOWING INFORMATION NOT SHOWN.
 PLEASE SEE MISSING CONDUCTORS FROM GUTTER TO METER AND
 TO MAIN.
 PLEASE SEE MISSING SIZE AND OVER CURRENT PROTECTION OF
 MAIN.
 PLEASE SE MISSING AIC RATING FOR NEW MAIN. (EVEN THOUGH
 NOTE IS ON 801 FOR OTHER EQUIPMENT).
 PLEASE INDICATE A "FOATING NEUTRAL"AT THE NEW METER.
 PLEASE REMOVE ALL REFERENCES TO "BUILDING #4"MAIN/
 SERVICE AS THERE IS ONLY ONE SERVICE ON THIS BUILDING.
 PLEASE SEE NOTES ON RISER.
 PLEASE PROVIDE THE COMPLETE RISER AND LOADS ON THE
 EXISTING RISER WITH NEW LOADS BEING ADDED.
  
 215.5, 215.3, 220.12, 220.14, 220.42, 220.42 ETC
 110.9, 250.6, 250.24B, ETC
 FBC 106.1.2 , 106.3.5.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORN,
 STROBES AND/OR HORN STROBE DEVICES PER FBC 11-4.28.1,
 .2 AND .3(4).
 THE INSTALLATION OF ANY ADDITIONAL DEVICES TO THE
 EXISTING FIRE ALARM SYSTEM WILL BE REQUIRED UNDER
 SEPARATE PLANS, PERMIT, HOWEVER THESE REQUIRED LEVELS
 ARE TO BE SHOWN ON BASE PLANS.
  
 8) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS EMERGENCY
 LIGHTS AND EXIT LIGHTS ON THEIR OWN CIRCUIT?
 PLEASE SEE 700.12E.
  
 9) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 106.1.2, 106.3.5.1.2
 NEC 408.4, 310.16, 240.4 FOR VERIFICATION.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT SUBMITTED A
 ND CHANGES IN PLANS WILL BE REQUIRED, THERE MAY BE
 COMMENTS ON THE NEXT REVIEW DUE TO ANY POSSIBLE
 CHANGES.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]