 BUILDING REVIEW COMMENTS
 ------------ ------------ ----------------
  
  
 ASPHALT SHINGLES ARE APPROVED,
  
 PROVIDE RAS 117 CALCULATIONS FOR APPROVAL AS REQUIRED
 IN GENERAL LIMITATIONS #7 ON THE GAF BUILT-UP (NOA),
  
 THE MAXIMUM DESIGN PRESSURES ARE -45 AND -75 ON THE
 REPORT PROVIDED, TABLE 1609.6B, 2004 FBC REQUIRES -89
 PSF IN ZONE 3.
  
  
  
  
  