2007-02-13 13:31:54BUILDING PLAN REVIEW
 PERMIT:06120649
 ADD: 741 ROSELAND DR
 CONT: SLATUR CONST
 TEL: (954) 938-4500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
  
 4)106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 5)WPB AMENDMENTS.106.1.3BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.THE BUILDING
 MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM.THIS
 POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENTS. THE DRAWINGS SHALL BE DRAFTSMAN QUALITY.
 THE DRAWINGS SUBMITTED ARE NOT ACCEPTABLE.
  
 6)WILL THE CARPORT BE CONVERTED INTO A GARAGE OR
 LIVING SPACE?
  
 7)106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILINDING OFFICIAL
  
 8)R309.1OPENINGS FROM A PRIVATE GARAGE DIRECTLY
 INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE
 PERMITTED, OTHER OPENINGS BETWEEN THE GARAGE AND
 RESIDENCE SHALL BEEQUIPPED WITH SOLID WOOD DOORS NOT
 LESS THAN 1 3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB
 CORE STEEL DOORS NOT LESS THAN 1 3/8 INCHES THICK, OR
 20-MINUTE FIRE-RATED DOORS.
  
 9)R309.2THE GARAGE SHALL BE SEPERATED FROM THE
 RESIDENCE AND ITS ATTIC AREA BY NOT LESS THAN 1/2-INCH
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPERATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5/8-INCH TYPE X
 GYPSUM BOARD OR EQUIVALENT.WHERE THE SEPERATION IS A
 FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE
 SEPERATIION SHALL ALSO BE PROTECTED BY NOT LESS THAN
 1/2 INCH GYPSUM BOARD OR EQUIVALENT.
  
 10)R309.3THE AREA OF FLOOR USED FOR PARKING OF
 AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO
 FACILICATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD
 THE MAIN VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 11)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO SETS OF UPDATED
 PRODUCT APPROVALS FOR EACH PRODUCT. SUBMIT A
 WINDOW/DOOR SCHEDULE WITH THE SIZE OF EACH OPENING. ON
 A FLOOR PLAN INDICATE THE LOACTION OF EACH WINDOW OR
 DOOR OPENING.
  
 12)IF THIS AREA WILL BE USED FOR LIVING SPACE, THE
 FLOOR WILL HAVE TO CONFORM TO THE REQUIREMENTS OF
 R506.1CONCRETE SLAB-ON-GROUND FLOORS SHALL BE A
 MINIMUM 3.5 INCHES (89 MM) THICK (FOR EXPANSIVE SOILS,
 SEE SECTION R403.1.8 ). THE SPECIFIED COMPRESSIVE
 STRENGTH OF CONCRETE SHALL BE AS SET FORTH IN SECTION
 R402.2 .
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER