2007-02-13 13:31:54 | BUILDING PLAN REVIEW |
| PERMIT:06120649 |
| ADD: 741 ROSELAND DR |
| CONT: SLATUR CONST |
| TEL: (954) 938-4500 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 1ST |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) 2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 3)110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| ) NUMBER OF UNITS |
| ) NUMBER OF FLOORS |
| ) NUMBER OF ROOMS |
| ) NUMBER OF BEDROOMS |
| ) SQ. FT. LIV SPACE/ FL |
| ) SQ. FT. FOOTPRINT |
| ) SQ. FT. UNDER ROOF (TOTAL) |
| |
| 4)106.1.2 ADDITIONAL DATA. THE |
| BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, |
| STRESS DIAGRAMS, AND OTHER |
| DATA NECESSARY TO DESCRIBE THE |
| CONSTRUCTION OR INSTALLATION AND THE |
| BASIS OF CALCULATION. ALL DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| REQUIRED BY THE BUILDING OFFICIAL TO BE |
| PREPARED BY AN ARCHITECT OR ENGINEER |
| SHALL BE AFFIXED WITH THIER OFFICIAL |
| SEAL, SIGNATURE AND DATE AS STATE LAW |
| REQUIRES. |
| |
| 5)WPB AMENDMENTS.106.1.3BUILDING PLANS SHALL BE |
| DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.THE BUILDING |
| MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS |
| FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM.THIS |
| POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENTS. THE DRAWINGS SHALL BE DRAFTSMAN QUALITY. |
| THE DRAWINGS SUBMITTED ARE NOT ACCEPTABLE. |
| |
| 6)WILL THE CARPORT BE CONVERTED INTO A GARAGE OR |
| LIVING SPACE? |
| |
| 7)106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILINDING OFFICIAL |
| |
| 8)R309.1OPENINGS FROM A PRIVATE GARAGE DIRECTLY |
| INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE |
| PERMITTED, OTHER OPENINGS BETWEEN THE GARAGE AND |
| RESIDENCE SHALL BEEQUIPPED WITH SOLID WOOD DOORS NOT |
| LESS THAN 1 3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB |
| CORE STEEL DOORS NOT LESS THAN 1 3/8 INCHES THICK, OR |
| 20-MINUTE FIRE-RATED DOORS. |
| |
| 9)R309.2THE GARAGE SHALL BE SEPERATED FROM THE |
| RESIDENCE AND ITS ATTIC AREA BY NOT LESS THAN 1/2-INCH |
| GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES |
| BENEATH HABITABLE ROOMS SHALL BE SEPERATED FROM ALL |
| HABITABLE ROOMS ABOVE BY NOT LESS THAN 5/8-INCH TYPE X |
| GYPSUM BOARD OR EQUIVALENT.WHERE THE SEPERATION IS A |
| FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE |
| SEPERATIION SHALL ALSO BE PROTECTED BY NOT LESS THAN |
| 1/2 INCH GYPSUM BOARD OR EQUIVALENT. |
| |
| 10)R309.3THE AREA OF FLOOR USED FOR PARKING OF |
| AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO |
| FACILICATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD |
| THE MAIN VEHICLES SHALL BE SLOPED TO FACILITATE THE |
| MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN |
| VEHICLE ENTRY DOORWAY. |
| |
| 11)106.3.3* PRODUCT APPROVALS- 2004 |
| THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITTING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. PROVIDE TWO SETS OF UPDATED |
| PRODUCT APPROVALS FOR EACH PRODUCT. SUBMIT A |
| WINDOW/DOOR SCHEDULE WITH THE SIZE OF EACH OPENING. ON |
| A FLOOR PLAN INDICATE THE LOACTION OF EACH WINDOW OR |
| DOOR OPENING. |
| |
| 12)IF THIS AREA WILL BE USED FOR LIVING SPACE, THE |
| FLOOR WILL HAVE TO CONFORM TO THE REQUIREMENTS OF |
| R506.1CONCRETE SLAB-ON-GROUND FLOORS SHALL BE A |
| MINIMUM 3.5 INCHES (89 MM) THICK (FOR EXPANSIVE SOILS, |
| SEE SECTION R403.1.8 ). THE SPECIFIED COMPRESSIVE |
| STRENGTH OF CONCRETE SHALL BE AS SET FORTH IN SECTION |
| R402.2 . |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |