Plan Review Notes
Plan Review Notes For Permit 06120640
Permit Number 06120640
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-18 10:14:01DENIED
 REFERENCE: FBC-2004 PLUMBING AND CITY OF WEST PALM
 BEACH AMENDMENTS TO FBC-2004, CHAPTER 1,
 ADMINISTRATION.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 107, TEMPORARY
 STUCTURES AND USES. SECTION 107.2 CONFORMANCE.
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 SANITARY AND WATER REQUIREMENTS OF THIS CODE AS
 NECESSARY TO ENSURE THE PUBLIC HEALTH, SAFETY AND
 GENERAL WELFARE.
  
 2. REQUIREMENTS: SITE PLAN INDICATING TRAILER LOCATION.
 TYPE OF PLUMBING HOOK-UP. IF WATER, INDICATE BACKFLOW
 LOCATION. IF SANITARY HOOK-UP AN ISOMETRIC SANITARY
 RISER DIAGRAM WITH SIZES REQUIRED. IF SANITARY
 DISCHARGES INTO A HOLDING TANK, PALM BEACH COUNTY
 HEALTH DEPARTMENT APPROVAL REQUIRED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721