2007-01-19 15:30:15 | *****DENIED***** |
| |
| |
| PLEASE BE ADVISED THAT THIS STRUCTURE SHALL BE |
| CLASSIFIED AS A NEW BUSINESS OCCUPANCY. |
| |
| |
| 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| |
| 02.THE SET-UP OR ERECTING OPERATIONS FOR THE |
| STRUCTURE SHALL NOTINTERFERE OR HINDER EMERGENCY |
| RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY |
| THEREOF (INCLUDING FIRE LANES). |
| |
| 03.FIRE DEPARTMENT ACCESS ROADSSHALL BE CAPABLE OF |
| SUPPORTING 32 TONS TO SUPPORT THE LOADS IMPOSED BY FIRE |
| APPARATUS/FIRE EQUIPMENT AND SHALL BE PROVIDED WITH A |
| SURFACE SUITABLE FOR ALL-WEATHER DRIVING CONDITIONS. |
| |
| 04.FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| UNOBSTRUCTED WIDTH OF NOT LESS THAN 20' AND AN |
| UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13' |
| 6IN". |
| |
| 05.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE |
| STRUCTURE ON THE PROPER EXTERIOR ELEVATION.AS PER |
| WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS |
| THAN 6" IN HEIGHT AND 1" IN WIDTH VISIBLE FROM THE |
| STREET OR ROADSIDE FRONTING THE STRUCTURE.[THE |
| APPLICABLE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET]. |
| |
| 06.INDICATE ON SITE PLAN THE DISTANCE OF THE |
| STRUCTURE TO THE NEAREST FIRE HYDRANT.PLEASE BE |
| ADVISED THAT IF THIS DISTANCE IS GREATER THAN 500 FEET, |
| AN ADDITIONAL FIRE HYDRANT MAY BE REQUIRED. |
| |
| 07.WILL THE STRUCTURE HAVE A FIRE ALARM AND/OR FIRE |
| SPRINKLER SYSTEM?IF SO, PLEASE PROVIDE A LAYOUT OF |
| THE FIRE PROTECTION SYSTEM(S). |
| |
| 08.WHAT IS THE MAXIMUM OCCUPANT LOAD FOR THE |
| STRUCTURE? |
| |
| 09.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY |
| LIGHTS, AND FIRE EXTINGUISHER(S). |
| |
| 10.PLEASE INDICATE THE LENGHT OF TIME THAT THIS |
| TEMPORARY STRUCTURE WILL BE USED. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| ITEM WAS ADDRESSED ON THE PLANS. |
| |
| |