Plan Review Notes For Permit 06120629 |
Permit Number |
06120629 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-09-04 18:14:25 | 2004 FBC | | 3RD REVIEW | | ADDITION AND REMODEL | | | | DENIED BY BUILDING | | | | 1) THE NOC THAT WAS SUBMITTED IS EXPIRED. IT WILL NEED | | TO BE RERECORDED BEFORE THE PERMIT IS ISSUED. | | | | 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY | | IMPACT FEES. ATTACH THE SHEETS WITH THE COUNTY IMPACT | | FEE STAMPS FROM THE OLD PLANS TO THE FRONT OF THE NEW | | PLANS OR HAVE THE NEW PLANS STAMPED BY THE COUNTY. | | | | 3) THE MAXIMUM DESIGNED PRESSURE SPECIFIED ON PAGE 28 | | OF -45 PSF FOR THE THE GAF MODIFIED ROOF SYSTEM NOA IS | | NOT ADEQUATE TO RESIST THE COMPONENT AND CLADDING WIND | | PRESSURES FOR EXPOSURE C . SEE FBC TABLE R301.2(2). THE | | DESIGN PRESSURES ARE LESS THAN REQUIRED FOR A FLAT ROOF | | IN ZONE C ( -107.7 PSF FOR ROOF ZONE 3 AND - 71.6 FOR | | ZONE 2) . SUBMIT RAS 117 CALCULATIONS FOR ENHANCED | | FASTENING AS ALLOWED BY LIMITATION #7 ON PAGE 32 OF THE | | NOA. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|