Plan Review Notes
Plan Review Notes For Permit 06120629
Permit Number 06120629
Review Stop B
Sequence Number 3
Notes
Date Text
2007-09-04 18:14:252004 FBC
 3RD REVIEW
 ADDITION AND REMODEL
  
 DENIED BY BUILDING
  
 1) THE NOC THAT WAS SUBMITTED IS EXPIRED. IT WILL NEED
 TO BE RERECORDED BEFORE THE PERMIT IS ISSUED.
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES. ATTACH THE SHEETS WITH THE COUNTY IMPACT
 FEE STAMPS FROM THE OLD PLANS TO THE FRONT OF THE NEW
 PLANS OR HAVE THE NEW PLANS STAMPED BY THE COUNTY.
  
 3) THE MAXIMUM DESIGNED PRESSURE SPECIFIED ON PAGE 28
 OF -45 PSF FOR THE THE GAF MODIFIED ROOF SYSTEM NOA IS
 NOT ADEQUATE TO RESIST THE COMPONENT AND CLADDING WIND
 PRESSURES FOR EXPOSURE C . SEE FBC TABLE R301.2(2). THE
 DESIGN PRESSURES ARE LESS THAN REQUIRED FOR A FLAT ROOF
 IN ZONE C ( -107.7 PSF FOR ROOF ZONE 3 AND - 71.6 FOR
 ZONE 2) . SUBMIT RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AS ALLOWED BY LIMITATION #7 ON PAGE 32 OF THE
 NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714