2007-06-22 08:14:48 | DENIED 2ND TIME |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OFDENIED REFERENCE: |
| FBC-2004 PLUMBING, FBC-2004 CHAPTER 1, CITY OF WEST |
| PALM BEACH AMENDMENTS, AND FLORIDA ADMINISTRATIVE |
| CODE. |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| MADE ON PREVIOUS REVIEWS. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| PREVIOUS REVIEW NOTES. |
| |
| A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| |
| AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| |
| A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| |
| ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| |
| 1. **NO**FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND |
| 417 FS, RESPECTIVELY. |
| |
| 2. **OK** |
| |
| 3. **NO/OK** SHEET M/P/E-1 WATER HEATER DETAIL, THE |
| FOLLOWING IS STILL REQUIRED AND NEEDS TO BE SHOWN ON |
| THE RESUBMITTAL: |
| A} **OK** |
| B} **OK** |
| C} **OK** |
| D} **OK** |
| E} **OK** |
| F} **OK** |
| G} **OK** |
| H} **NO** PER FBC-2004 PLUMBING, SECTION 607.3, |
| THERMAL EXPANSION CONTROL REQUIRED. PLEASE ADD THE |
| THERMAL EXPANSION PROTECTION ON THE RESUBMITTED WATER |
| HEATER DETAIL. |
| |
| THE FOLLOWING ARE NEW ITEMS: |
| |
| 4. SHEET M/P/E-1 ELECTRIC WATER HEATER DETAIL: THE |
| NEWLY SUBMITTED ELECTRIC WATER HEATER DETAIL IS |
| INDICATING A BOTTOM FED WATER HEATER. PLEASE ADD THE |
| FOLLOWING FOR THIS HEATER PER FBC-2004 PLUMBING, |
| SECTION 504.2 A BOTTOM FED WATER HEATER SHALL HAVE A |
| VACUUM RELIEF VALVE INSTALLED. THE VACUUM RELIEF SHALL |
| COMPLY WITH ANSI Z21.22. PLEASE INDICATE THIS ON THE |
| RESUBMITTAL. |
| |
| 5. SHEET M/P/E-1 PLUMBING RISER: THE RESUBMITTED |
| ISOMETRIC RISER DIAGRAM IS INDICATING A 4" X 4" X 3" |
| COMBINATION-WYE AND EIGHTH BEND TO THE WATER CLOSET. |
| PLEASE DELETE THIS AND THE OFFSET TO THE WATER CLOSET |
| AND ADD A 4" QUARTER BEND IN ITS PLACE FOR THE |
| RESUBMITTAL. |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |