Plan Review Notes
Plan Review Notes For Permit 06120629
Permit Number 06120629
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-22 08:14:48DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OFDENIED REFERENCE:
 FBC-2004 PLUMBING, FBC-2004 CHAPTER 1, CITY OF WEST
 PALM BEACH AMENDMENTS, AND FLORIDA ADMINISTRATIVE
 CODE.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO**FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND
 417 FS, RESPECTIVELY.
  
 2. **OK**
  
 3. **NO/OK** SHEET M/P/E-1 WATER HEATER DETAIL, THE
 FOLLOWING IS STILL REQUIRED AND NEEDS TO BE SHOWN ON
 THE RESUBMITTAL:
 A} **OK**
 B} **OK**
 C} **OK**
 D} **OK**
 E} **OK**
 F} **OK**
 G} **OK**
 H} **NO** PER FBC-2004 PLUMBING, SECTION 607.3,
 THERMAL EXPANSION CONTROL REQUIRED. PLEASE ADD THE
 THERMAL EXPANSION PROTECTION ON THE RESUBMITTED WATER
 HEATER DETAIL.
  
 THE FOLLOWING ARE NEW ITEMS:
  
 4. SHEET M/P/E-1 ELECTRIC WATER HEATER DETAIL: THE
 NEWLY SUBMITTED ELECTRIC WATER HEATER DETAIL IS
 INDICATING A BOTTOM FED WATER HEATER. PLEASE ADD THE
 FOLLOWING FOR THIS HEATER PER FBC-2004 PLUMBING,
 SECTION 504.2 A BOTTOM FED WATER HEATER SHALL HAVE A
 VACUUM RELIEF VALVE INSTALLED. THE VACUUM RELIEF SHALL
 COMPLY WITH ANSI Z21.22. PLEASE INDICATE THIS ON THE
 RESUBMITTAL.
  
 5. SHEET M/P/E-1 PLUMBING RISER: THE RESUBMITTED
 ISOMETRIC RISER DIAGRAM IS INDICATING A 4" X 4" X 3"
 COMBINATION-WYE AND EIGHTH BEND TO THE WATER CLOSET.
 PLEASE DELETE THIS AND THE OFFSET TO THE WATER CLOSET
 AND ADD A 4" QUARTER BEND IN ITS PLACE FOR THE
 RESUBMITTAL.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721