Plan Review Notes
Plan Review Notes For Permit 06120629
Permit Number 06120629
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-13 07:38:39 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS. SEE 230.70 FOR
 DISCONNECT REQUIREMENTS. IT APPEARS AS THOUGH THE
 ENTRANCE CONDUCTORS WILL BE ROUTED OVERHEAD GIVEN THE
 LOCATIION OF THE PANEL WITH RESPECT TO THE RELOCATED
 SERVICE, THEREFORE A DISCONNECT WOULD BE NEEDED AT THE
 METER. INDICATE IF OVERHEAD OR UNDER GROUND, THE NOTE
 AT THE RISER AND THE RISER DIAGRAM ARE IN CONFLICT.
  
 3} SEE ARTICLE 250.66 FOR GEC SIZE, 250.50 FOR GEC
 REQUIREMENTS, ESPECIALLY NOTE 250.52(A)(3), CONCRETE
 ENCASED, SINCE AVAILABLE, WILL BE REQUIRED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS." THE SCUDULE PROVIDED
 HDOES NOT LIST THE REQUIRED CIRCUITS PER ARTICLE 210.
 ALSO THE SCHEDULE SHOWS NO AHU, THERE ARE 2 WATER
 HEATERS IN THE CALCS, NONE ON THE SCHEDULE,
 DISHWASHER/DISPOSAL, WHIRLPOOL, NO REQUIRED BATH
 CIRCUIT(210.11(C)(3),
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]