2007-06-13 07:38:39 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| FS, RESPECTIVELY. |
| |
| 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| SIZE AND TYPE, GROUNDING DETAILS. SEE 230.70 FOR |
| DISCONNECT REQUIREMENTS. IT APPEARS AS THOUGH THE |
| ENTRANCE CONDUCTORS WILL BE ROUTED OVERHEAD GIVEN THE |
| LOCATIION OF THE PANEL WITH RESPECT TO THE RELOCATED |
| SERVICE, THEREFORE A DISCONNECT WOULD BE NEEDED AT THE |
| METER. INDICATE IF OVERHEAD OR UNDER GROUND, THE NOTE |
| AT THE RISER AND THE RISER DIAGRAM ARE IN CONFLICT. |
| |
| 3} SEE ARTICLE 250.66 FOR GEC SIZE, 250.50 FOR GEC |
| REQUIREMENTS, ESPECIALLY NOTE 250.52(A)(3), CONCRETE |
| ENCASED, SINCE AVAILABLE, WILL BE REQUIRED. |
| |
| 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| DISTINGUISHED FROM ALL OTHERS." THE SCUDULE PROVIDED |
| HDOES NOT LIST THE REQUIRED CIRCUITS PER ARTICLE 210. |
| ALSO THE SCHEDULE SHOWS NO AHU, THERE ARE 2 WATER |
| HEATERS IN THE CALCS, NONE ON THE SCHEDULE, |
| DISHWASHER/DISPOSAL, WHIRLPOOL, NO REQUIRED BATH |
| CIRCUIT(210.11(C)(3), |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW. |