2007-07-09 15:42:29 | DENIED BY BUILDING |
| |
| 1) THE NOC THAT WAS SUBMITTED IS EXPIRED. IT WILL NEED |
| TO BE RERECORDED BEFORE THE PERMIT IS ISSUED. |
| |
| 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY |
| IMPACT FEES. ATTACH THE SHEETS WITH THE COUNTY IMPACT |
| FEE STAMPS FROM THE OLD PLANS TO THE FRONT OF THE NEW |
| PLANS OR HAVE THE NEW PLANS STAMPED BY THE COUNTY. |
| |
| 3) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED |
| BY THE PREPARER PER FBC CHAPTER 13. |
| |
| 4) BATHROOM DOOR NUMBER 10 ON THE SCHEDULE DOES NOT |
| COMPLY WITH R322.1.1 FOR ACCESSIBILITY, WHICH REQUIRES |
| AT LEAST ONE BATHROOM WITH A DOOR THAT HAS A 29" CLEAR |
| OPENING. |
| THE 29 " CLEAR OPENING IS WITH THE DOOR OPEN 90 DEGREES |
| MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE |
| STOP. SEE R322.2.2 AND FBC 11-4.13.5. |
| |
| 5) THE TRUSS LAYOUT IS REQUIRED TO BE SIGNED, SEALED |
| AND DATED BY THE TRUSS ENGINEER, IN ADDITION TO BEING |
| REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE |
| STRUCTURE. |
| FS 471 |
| |
| 6) THE TRUSS DRAWINGS ARE REQUIRED TO BE SIGNED BY THE |
| TRUSS ENGINEER, SIGNATURE STAMPS ARE NOT ACCEPTABLE. FS |
| 471 AND FAC 61G15-23.002. |
| NOTE: TRUSS LAYOUT AND DRAWINGS CAN BE SUBMITTED THE |
| INSPECTOR IN THE FIELD AT TIME OF TRUSS INSPECTION. |
| |
| 7) SPECIFY WHICH ONE OF THE FASTENING OPTIONS AND |
| DESIGN PRESSURES ON PAGE 28 OF THE NOAWILL BE USED TO |
| INSTALL THE GAF MODIFIED ROOF SYSTEM. CIRCLE THE |
| APPROPRIATE ONE ON THE NOA. THE DESIGN PRESSURES ARE |
| LESS THAN REQUIRED FOR A FLAT ROOF IN ZONE C ( -107.7 |
| PSF FOR ROOF ZONE 3 AND - 71.6 FOR ZONE 2) . SUBMIT RAS |
| 117 CALCULATIONS FOR ENHANCED FASTENING AS ALLOWED BY |
| LIMITATION #7 ON PAGE 32 OF THE NOA. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |