Plan Review Notes
Plan Review Notes For Permit 06120599
Permit Number 06120599
Review Stop B
Sequence Number 2
Notes
Date Text
2007-02-01 18:13:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)FIRST APPLICATION USED THE MOST STRINGENT
 CONDITION FOR DESIGN PRESSSURES, FULLY ENCLOSED.IN
 THE NEW ENGINEERING YOU HAVE CIRCLED BOTH BUT HAVE
 WRITTEN THE LESS STRINGENT CONDITION ON THE
 INSTALLATION SCHEDULE.IF YOU ARE TO USE THE LESS
 STRINGENT PRESSURES, SEE ENGINEER'S NOTE 2G.THIS IS
 TO BE DETERMINED BY AN ARCHITECT OR ENGINEER.
 CALCULATIONS SHOWING THAT THIS IS A PARTIALLY ENCLOSED
 BUILDING WILL BE REQUIRED FOR YOU TO USE THESE
 PRESSURES.
  