Plan Review Notes
Plan Review Notes For Permit 06120593
Permit Number 06120593
Review Stop P
Sequence Number 1
Notes
Date Text
2007-02-06 14:12:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-03 SHOW THE CLEAR FLOOR SPACE FOR THE KITCHEN
 SINK PER SECTION 11-4.24.5. FORWARD APPROACH REQUIRED
 AND SHALL EXTEND A MAXIMUM 19" UNDERNEATH THE SINK.
 CABINET DOORS ARE NOT ALLOWED IN THE CLEAR FLOOR SPACE
 OF THE SINK. DELETE FROM CABINET DETAIL.
  
 2. SHT A-08 DETAIL. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 3. SHT P0.1 WATER RISER DIAGRAM. THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE, IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS. (ALSO SEE
 PLUMBING NOTE #13).
  
 4. ALL ARCHITECTURAL SHEETS. A TITLE BLOCK MUST APPEAR
 ON ALL ARCHITECTURAL DRAWINGS AND SPECIFICATION
 IDENTIFICATIONS SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 PLEASE MAKE SURE ALL INFORMATION IS IN THE TITLE BLOCK
 ON EACH SHEET. FAC 61G1-16.004 & FS 481.219, 481.2055.
  
 5. THE ADDRESS OF THE BUILDING SHALL BE INDICATED ON
 THE PLANS. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]