Date |
Text |
2007-01-12 11:45:28 | |
| ** UNSAT ** |
| |
| |
| 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM |
| TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING |
| SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION. |
| FAC 61G1-16.004, FAC61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A |
| TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE |
| ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS |
| INFORMATION ETC. |
| PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM |
| IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE |
| REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION |
| NUMBER. (THIS HAS ALREADY BEEN GONE OVER WITH STAFF |
| FROM PBM AND IT IS OUR UNDERSTANDING THAT APPLICATION |
| TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| REGULATIONS HAS/IS TAKING OR TAKEN PLACE. |
| PLEASE KNOW IF PERMIT ISSUANCE IS DOWN TO ONLY THIS |
| COMMENT AND THE CERTIFICATE OF AUTHORIZATION NUMBER HAS |
| NOT YET BEEN ISSUED FROM THE STATE, THE TITLE BLOCKS |
| WOULD BE REVISED TO BE LISTED WITH THE ARCHITECT ONLY. |
| FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA |
| STATUTES 481.219 |
| **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, |
| HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER |
| ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| TRADE. |
| |
| 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES |
| RELEVANT TO THIS PROJECT AND DESIGN. |
| 2002 NFPA-72, 2005 NFPA-70, 2003 NFPA-101 |
| PLEASE SEE AS THE PERMIT WAS APPLIED FOR ON OR AFTER |
| DECEMBER 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC |
| AND THE 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY |
| THE STATE OF FLORIDA. |
| PLEASE ADJUST CODES ON PLANS. |
| |
| 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL |
| PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER |
| RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON |
| "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL |
| LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES |
| FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS |
| MAX FOR TIMER TYPE) |
| PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM. |
| PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT |
| PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE |
| SEE STORAGE) |
| PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM |
| PERMITTED LIGHTING POWER DENSITIES. |
| PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY |
| CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT. |
| ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET |
| SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT |
| BE FULLY ACCOMPLISHED AT THIS TIME. |
| |
| 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY |
| AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE |
| CONTROL DEVICES PER 700.12E. PLEASE SEE A |
| CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS |
| BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT |
| LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER |
| DEVICES. |
| |
| 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| 215.3, 230.42 ETC. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE |
| FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS |
| AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.) |
| 408.4. |
| ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN. |
| |
| 8) NOTE:PLEASE SEE THE ADDRESS OF THE PROJECT IS |
| MISSING FROM TITLE BLOCKS. THE SUITE # OF 440 IS OK FOR |
| SUITE, NEEDS ADDRESS OF 444 RAILROAD AVE. |
| |
| 9) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| SHEETS FOR THE NEW INSTA-HOT TANKLESS WATER HEATER. |
| PLEASE SEE PLUMBING REVIEW COMMENTS FOR THIS AND PLEASE |
| BE SURE A LISTING FROM A NRTL IS ON PLANS. |
| |
| 10) NOTE: |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY |
| ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |