Plan Review Notes
Plan Review Notes For Permit 06120593
Permit Number 06120593
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-22 16:53:01BUILDING PLAN REVIEW
 PERMIT: 06120593
 ADD: 444 W. RAILROAD SUITE 440
 CONT: PBM DEVELOPMENT
 TEL: (561)715-1800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PBM DEVELOPMENT IF ACTING AS AN ARCHITECTURAL FIRM
 WILL REQUIRE A CERTIFICATE OF AUTHORIZATION.
 FAC 481.219(2)(3).
  
 3) SHEET A-08 KITHEN DETAIL INDICATES THE USE OF A
 KITHEN SINK. SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE SINK.
  
 4) NOTE: THE PLANS , VARIOUS WALL SECTIONS INDICATE THE
 USE
 OF CROWN MOLDING, THE TYPE OF MATERIAL IS NOT INDICATED
 ON THE PLAN ,
 2604.2 INTERIOR TRIM.
 FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH
 SECTIONS 2604.2.1 THROUGH 2604.2.4 .
  
 2604.2.1 DENSITY.
 THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20
 PCF (320 KG/M 3 ).
  
 2604.2.2 THICKNESS.
 THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5
 INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES
 (204 MM).
  
 2604.2.3 AREA LIMITATION.
 THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10
 PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY
 ROOM OR SPACE.
  
 2604.2.4 FLAME SPREAD.
 THE FLAME SPREAD INDEX SHALL NOT EXCEED 75 WHERE TESTED
 IN ACCORDANCE WITH ASTM E 84. THE SMOKE-DEVELOPED INDEX
 SHALL NOT BE LIMITED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  