2007-01-22 16:53:01 | BUILDING PLAN REVIEW |
| PERMIT: 06120593 |
| ADD: 444 W. RAILROAD SUITE 440 |
| CONT: PBM DEVELOPMENT |
| TEL: (561)715-1800 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) PBM DEVELOPMENT IF ACTING AS AN ARCHITECTURAL FIRM |
| WILL REQUIRE A CERTIFICATE OF AUTHORIZATION. |
| FAC 481.219(2)(3). |
| |
| 3) SHEET A-08 KITHEN DETAIL INDICATES THE USE OF A |
| KITHEN SINK. SINKS: |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| APPROACH. |
| THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE |
| AND |
| SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH |
| THE SINK. |
| |
| 4) NOTE: THE PLANS , VARIOUS WALL SECTIONS INDICATE THE |
| USE |
| OF CROWN MOLDING, THE TYPE OF MATERIAL IS NOT INDICATED |
| ON THE PLAN , |
| 2604.2 INTERIOR TRIM. |
| FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH |
| SECTIONS 2604.2.1 THROUGH 2604.2.4 . |
| |
| 2604.2.1 DENSITY. |
| THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20 |
| PCF (320 KG/M 3 ). |
| |
| 2604.2.2 THICKNESS. |
| THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5 |
| INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES |
| (204 MM). |
| |
| 2604.2.3 AREA LIMITATION. |
| THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10 |
| PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY |
| ROOM OR SPACE. |
| |
| 2604.2.4 FLAME SPREAD. |
| THE FLAME SPREAD INDEX SHALL NOT EXCEED 75 WHERE TESTED |
| IN ACCORDANCE WITH ASTM E 84. THE SMOKE-DEVELOPED INDEX |
| SHALL NOT BE LIMITED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |