Plan Review Notes
Plan Review Notes For Permit 06120592
Permit Number 06120592
Review Stop P
Sequence Number 2
Notes
Date Text
2007-02-03 09:06:43DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTES #1 AND #3.
 2. PAGE P0.1 PLUMBING NOTE # 11 PLEASE CHANGE NOTE
 SINCE THE AREA ABOVE THE DROP CEILING IS A PLENUM TO
 READ NO PVC PERMITED. PIPING MATERIAL TO BE CAST IRON
 OR COPPER DWV TYPE.
 3.PREVIOUS NOT #3 FROM LAST REVIEW, THE WATER HAMMER
 ARRESTOR TO BE INSTALLED PER MANUFACTURE'S INSTALLATION
 INSTRUCTIONS, AS CLOSE TO THE SOURCE (FIXTURE) AS
 POSSIBLE. ONE RISER DIAGRAM MARKED IN RED.
 PLUMBING PLAN REVIEW BY;