Plan Review Notes For Permit 06120592 |
Permit Number |
06120592 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-01-25 16:41:22 | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW NOTES #1 AND 3, PLEASE | | CORRECT. | | | | 2)PAGES A-05 AND A-08 SHOW THE SPACE ABOVE THE | | ACCOUSTIC TILE CEILING TO BE AN OPEN PLENUM AND WOULD | | NOT REQUIRE RETURN AIR TRANSFER DUCTS, IF THIS IS SO | | PLEASE DO NOT SHOW RETURN AIR TRANSFER DUCTS ON PAGE | | M-2.1. IF NOT AN OPEN PLENUM RETURN AIR TRANSFER DUCTS | | TO OFFICES 2,3,4,5, AND CONFERENCE ROOM, ARE | | UNDER-SIZED. BALANCED RETURN AIR MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | INCREASING THE RETURN TRANSFER ONE AND | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING | | AND THE DOOR HAVING AT LEAST AN | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | PROPER RETURN AIR BALANCE. PER 2004 FBC/M 601.4. PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|