Plan Review Notes For Permit 06120592 |
Permit Number |
06120592 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-16 07:42:48 | DENIED; | | 1.ADD MISSING INFORMATION TO TITLE BLOCK. SEE | | ELECTRICAL PLAN REVIEW NOTES 1 & 2. | | 2.BREAK SINK MUST COMPLY TO THE FBC-2004 BUILDING | | CHAPTER 11 ACCESSIBILITY CODE. THE ELEVATION (4) PAGE | | A-06 DOES NOT COMPLY. | | 11-4.24.2 HEIGHT OF SINK IS 34". | | 11-4.24.3 KNEE CLEARANCE 27" HIGH, 30" | | WIDE, AND 19" DEEP. (NO CABINET DOORS) | | 11-4.24.4 DEPTHMAX 6 1/2" DEEP. | | 11-4.24.5 CLEAR FLOOR SPACE 30 X 48 SHOW | | ON FLOOR PLAN. | | 11-4.24.6 INSULATE EXPOSED PIPES. 3.WATER | | RISER, WATER HAMMER ARRESTOR TO BE INSTALLED PER | | MANUFATURE'S SPECS,CLOSE TO THE SOURCE (SHOW AT | | BOTTOM OF DROP) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|