Plan Review Notes
Plan Review Notes For Permit 06120592
Permit Number 06120592
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-16 07:42:48DENIED;
 1.ADD MISSING INFORMATION TO TITLE BLOCK. SEE
 ELECTRICAL PLAN REVIEW NOTES 1 & 2.
 2.BREAK SINK MUST COMPLY TO THE FBC-2004 BUILDING
 CHAPTER 11 ACCESSIBILITY CODE. THE ELEVATION (4) PAGE
 A-06 DOES NOT COMPLY.
 11-4.24.2 HEIGHT OF SINK IS 34".
 11-4.24.3 KNEE CLEARANCE 27" HIGH, 30"
 WIDE, AND 19" DEEP. (NO CABINET DOORS)
 11-4.24.4 DEPTHMAX 6 1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE 30 X 48 SHOW
 ON FLOOR PLAN.
 11-4.24.6 INSULATE EXPOSED PIPES. 3.WATER
 RISER, WATER HAMMER ARRESTOR TO BE INSTALLED PER
 MANUFATURE'S SPECS,CLOSE TO THE SOURCE (SHOW AT
 BOTTOM OF DROP)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695