2007-01-08 14:06:33BUILDING PLAN REVIEW
 PERMIT: 06120592
 ADD: 444 W RAILROAD AVESUITE 450
 CONT: PBM DEVELOPMENT
 TEL: (561)368-2544
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PBM DEVELOPMENT, INC. ACTING AS AN ARCHITECTURAL
 FIRM MUST AQUIRE A CERTIFICATE OF AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) THE TITLEBLOCK IS MISSING THE LOCATION OF
 THE JOB, ONLY THE SUITE NUMBER HAS BEEN
 PROVIDED. SEE FL S S 61G1-16.004 TITLE BLOCK(3)
 IDENTIFICATIOJN OF PROPERTY.
  
 4) SHEET A-03106.1.2 ADDITIONAL INFORMATION REQUIRED.
 THE
 FLOOR PLAN DOESN'T INDICATE DOOR SWINGS WITHIN THE
 UNIT.
 IT APPEARS CONFERENCE ROOM 454 MAY HAVE A
 PAIR OF 30" DOORS. SEE SECTION 11-4.13.4 DOUBLE-LEAF
 DOORWAYS.
 IF DOORWAYS HAVE TWO INDEPENDENTLY OPERATED DOOR
 LEAVES,
 THEN AT LEAST ONE LEAF SHALL MEET THE SPECIFICATIONS
 IN
 SECTION 11-4.13.5 AND SECTION 11-4.13.6 . THAT LEAF
 SHALL BE AN ACTIVE LEAF.
  
 5)SHEET A-04 IS MISSING EMERGENCY LIGHTING
 REQUIREMENTS SEE TABLE
 1006, BUSINESS > 2 STORIES ABOVE GRADE LED
  
 6) SHEET A-04 1006.3.1
 EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT SIGN SHALL BE
 SUITABLY ILLUMINATED
 BY A RELIABLE LIGHT SOURCE. EXTERNALLY AND INTERNALLY
 ILLUMINATED SIGNS
 SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY
 LIGHTING.
  
  
 7) SHEET A-05 & A-06 BOTH INDICATE CHAIR RAIL AND CROWN
 TRIM, BUT NO MENTION AS TO TYPE OF MATERIAL. 805.3 FOAM
 PLASTIC USED AS TRIM IN ANY OCCUPANCY SHALL
  
 COMPLY WITH SECTION 2604.2 . 2604.2 INTERIOR TRIM. FOAM
 PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH
 SECTIONS 2604.2.1 THROUGH 2604.2.4 .
 2604.2.1 DENSITY.
 THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20
 PCF (320 KG/M 3 ).
 2604.2.2 THICKNESS.
 THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5
 INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES
 (204 MM).
 2604.2.3 AREA LIMITATION.
 THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10
 PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY
 ROOM OR SPACE.
 2604.2.4 FLAME SPREAD.
 THE FLAME SPREAD INDEX SHALL NOT EXCEED 75 WHERE TESTED
 IN ACCORDANCE WITH ASTM E 84. THE SMOKE-DEVELOPED INDEX
 SHALL NOT BE LIMITED.
  
 8) SHEETS A-05 & A-06 BOTH ALSO INDICATE THE USE OF
 GLAZING NEXT TO DOORWAYS, PLANS DO NOT INDICATE WHAT
 TYPE OF GLAZING SHALL BE USED.
 2406.3 HAZARDOUS LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS:
 1.GLAZING IN SWINGING DOORS EXCEPT JALOUSIES (SEE
 SECTION 2406.3.1 ).
 2.GLAZING IN FIXED AND SLIDING PANELS OF SLIDING
 DOOR ASSEMBLIES AND PANELS IN SLIDING AND BIFOLD CLOSET
 DOOR ASSEMBLIES.
 3.GLAZING IN STORM DOORS.
 4.GLAZING IN UNFRAMED SWINGING DOORS.
 5.GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS,
 WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS.
 GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING
 THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A
 STANDING SURFACE.
 6.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL
 ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF
 THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER
 VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND
 WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS
 THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE.
  
 9) A-06 INDICATES THE USE OF A BREAKROOM SINK, NO
 ACCESSIBILITY.
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  