2008-07-24 09:20:02 | ** DENIED REVIEW ** |
| |
| ** THERE ARE COMMENTS WHICH COME FROM PREVIOUS REVIEW |
| COMMENTS HOWEVER THEY ARE NEW BASED ON INFORMATION NOW |
| ON PLANS. |
| THERE ARE ALSO SOME REPEAT COMMENTS |
| |
| 1) NOTE: PLEASE SEE THE NEW SERVICE ENTRANCE CONDUCTORS |
| WHICH ARE NOW BEING SHOWN ARE NOT COMPLETE. NO CONDUIT |
| SIZE IS SHOWN. THE REVIEW FOR CODE COMPLIANCE FOR |
| CONDUIT FILL CAN NOT BE DONE. (TABLE 9) |
| |
| 2) NOTE: PLEASE ALSO SEE THE NEW SERVICE ENTRANCE |
| CONDUCTORS DO NOT MEET THE MINIMUM SIZE REQUIRED PER |
| 240.4B FOR DEVICES OVER 800AMPS. |
| PLEASE ADJUST. 310.16 |
| |
| 3) NOTE: PLEASE SUPPLY AIC RATING OF THE 1200AMP MAIN |
| AS PREVIOUSLY REQUESTED. |
| 110.9. |
| PLANS NOTE AIC RATING OF PANELS AND BREAKERS HOWEVER |
| DOES NOT INDICATE MAIN RATING. |
| |
| 4) NOTE: PLEASE SEE UNIT B ON E-3 WHICH IS SHOWING SD |
| FOR SMOKE DETECTOR. THIS CAN BE REDLINED AND DOES NOT |
| NEED TO REPRINT SHEETS AT THIS TIME. |
| |
| |
| |
| IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |