Plan Review Notes
Plan Review Notes For Permit 06120586
Permit Number 06120586
Review Stop E
Sequence Number 3
Notes
Date Text
2008-07-24 09:20:02** DENIED REVIEW **
  
 ** THERE ARE COMMENTS WHICH COME FROM PREVIOUS REVIEW
 COMMENTS HOWEVER THEY ARE NEW BASED ON INFORMATION NOW
 ON PLANS.
 THERE ARE ALSO SOME REPEAT COMMENTS
  
 1) NOTE: PLEASE SEE THE NEW SERVICE ENTRANCE CONDUCTORS
 WHICH ARE NOW BEING SHOWN ARE NOT COMPLETE. NO CONDUIT
 SIZE IS SHOWN. THE REVIEW FOR CODE COMPLIANCE FOR
 CONDUIT FILL CAN NOT BE DONE. (TABLE 9)
  
 2) NOTE: PLEASE ALSO SEE THE NEW SERVICE ENTRANCE
 CONDUCTORS DO NOT MEET THE MINIMUM SIZE REQUIRED PER
 240.4B FOR DEVICES OVER 800AMPS.
 PLEASE ADJUST. 310.16
  
 3) NOTE: PLEASE SUPPLY AIC RATING OF THE 1200AMP MAIN
 AS PREVIOUSLY REQUESTED.
 110.9.
 PLANS NOTE AIC RATING OF PANELS AND BREAKERS HOWEVER
 DOES NOT INDICATE MAIN RATING.
  
 4) NOTE: PLEASE SEE UNIT B ON E-3 WHICH IS SHOWING SD
 FOR SMOKE DETECTOR. THIS CAN BE REDLINED AND DOES NOT
 NEED TO REPRINT SHEETS AT THIS TIME.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  