Plan Review Notes
Plan Review Notes For Permit 06120586
Permit Number 06120586
Review Stop M
Sequence Number 2
Notes
Date Text
2007-11-27 08:23:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER
 2004 FBC 13-600.3.A, (12-8-06 REVISION). NOT 2001.
  
 2 ENERGY CALCULATIONS NEED TO BE SIGNED BY THE PREPARER
 AND THE OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2.
  
 3) COULD NOT FIND THE A/C SYSTEMS LISTED ON THE
 MECHANICAL PLANS (PAGE M-1 & M-2) ON THE ARI DIRECTORY
 WEB SITE. PLEASE SUBMIT THE ARI REFERENCE NUMBER OR A
 COPY OF THE ARI PERFORMANCE CERTIFICATE, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 4) LAST REVIEW 1-22-07 NOTE #7 STATED THE RETURN AIR
 TRANSFER DUCTS WERE UNDER SIZED, THIS WAS IN REFERENCE
 TO THE FLEX DUCTS NOT THE GRILLS, PLEASE BE ADVISED IF
 THEY REMAIN THE SAME A PRESSURE DIFFERENTIAL TEST WILL
 BE DONE AT FINAL INSPECTION AND CORRECTIONS MAY BE
 REQUIRED, SEE 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]