Plan Review Notes For Permit 06120586 |
Permit Number |
06120586 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-27 08:23:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER | | 2004 FBC 13-600.3.A, (12-8-06 REVISION). NOT 2001. | | | | 2 ENERGY CALCULATIONS NEED TO BE SIGNED BY THE PREPARER | | AND THE OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2. | | | | 3) COULD NOT FIND THE A/C SYSTEMS LISTED ON THE | | MECHANICAL PLANS (PAGE M-1 & M-2) ON THE ARI DIRECTORY | | WEB SITE. PLEASE SUBMIT THE ARI REFERENCE NUMBER OR A | | COPY OF THE ARI PERFORMANCE CERTIFICATE, SEE 2004 FBC | | 13-607.1.ABC.3.1.1. | | | | 4) LAST REVIEW 1-22-07 NOTE #7 STATED THE RETURN AIR | | TRANSFER DUCTS WERE UNDER SIZED, THIS WAS IN REFERENCE | | TO THE FLEX DUCTS NOT THE GRILLS, PLEASE BE ADVISED IF | | THEY REMAIN THE SAME A PRESSURE DIFFERENTIAL TEST WILL | | BE DONE AT FINAL INSPECTION AND CORRECTIONS MAY BE | | REQUIRED, SEE 2004 FBC/R M1602.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|