Plan Review Notes
Plan Review Notes For Permit 06120586
Permit Number 06120586
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-29 12:29:06** DENIED 2ND REVIEW **
  
 ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW AS THERE
 WERE CHANGES WHICH WERE NEEDED AND ITEMS NOT SUBMITTED
 ON PREVIOUS PLANS THERE MAY BE NEW COMMENTS GENERATED
 ON THE 2ND REVIEW.
 ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS
 SUBMITTED AND SOME ITEMS FROM PREVIOUS REVIEW WHICH
 STILL NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS.
  
  
 1) NOTE: PLEASE SEE AS MENTIONED ON PREVIOUS REVIEW
 NOTE # 27 THE ADDRESS WAS YET TO BE DETERMINED AND LOOK
 FOR COMMENTS FROM THE ADDRESSING REVIEWER.
 PLEASE SEE THE NEW ADDRESS OF 1810 EMBASSY DR WAS
 GENERATED. AS THESE ARE NOT FEE SIMPLE TOWNHOUSES AND
 PLANS HAVE HAD CHANGES INDICATING THIS, PLEASE ADJUST
 ADDRESS IN TITLE BLOCKS TO 1810.
  
 2) NOTE: PLEASE SEE AS PREVIOUSLY MENTIONED IN NOTE #2,
 PLEASE BE SURE ALL SMOKE ALARMS MEET NFPA-72 11.8.3
 WHICH REQUIRES ALL SMOKE DEVICES TO BE A MINIMUM OF 3FT
 FROM BATH DOORS AND 20FT FROM COOKING APPLIANCES. THERE
 ARE EXCEPTIONS FOR COOKING APPLIANCES IF DEVICE IS OF A
 PHOTO-ELECTRIC TYPE AND/OR RESETTING TYPE.
 PLEASE SEE UNIT A MASTER BEDROOM FOR EXAMPLE.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES # 3, #4 AND #10.
 PLEASE SEE THERE ARE STILL SOME AREAS WHERE SOME GFI
 RECEPTACLES DO NOT MEET 210.52C1-5 AND 210.8A6.
 PLEASE SEE E-2 UNIT A, ISLAND FOR ONE EXAMPLE. (GFI)
 PLEASE SEE E-2 UNIT A,PENINSULAR AND SEPARATE SPACES
 AND COUNTER SPACE FOR EXAMPLE.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE #8 FOR LISTING OF ALL
 RELEVANT CODES WHICH WERE REQUIRED TO BE ADJUSTED AND
 PLACED ON PLANS.
 RESPONSE WAS THAT ALL CODES WERE ADDED TO A AND SHEET
 E-4, WHICH WAS OK AND CORRECT HOWEVER PLEASE SEE E-2
 AND E-3 AS THE 2002 NFPA-70 ( NEC) IS STILL REFERENCED
 IN NOTES.
 PLEASE ADJUST.
  
 5) NOTE: PLEASE KNOW AS MENTIONED IN PREVIOUS REVIEW
 NOTES #11,12 ETC THE SERVICE WAS CHANGED FROM PREVIOUS
 PLANS AND NEW COMMENTS ARE NOW BEING MADE.
 PLEASE SEE THE FOLLOWING COMMENTS FOR SERVICE RISER:
 NOTES 6-11
  
 6) NOTE: PLEASE SEE MISSING CONDUITS FROM FPL TO
 SERVICE. AS FPL DOES NOT INSTALL THESE CONDUITS, THESE
 FALL UNDER THE NEC AND SIZING REQUIREMENTS FOR
 SERVICE.
 ***IMPORTANT: PLEASE VERIFY WITH THE FPL SERVICE
 PLANNER THAT THE SERVICE ENTRANCE CONDUCTORS ARE
 ACTUALLY GOING TO BE PULLED IN AND INSTALLED BY FPL.
 ALMOST ALL PROJECTS WHERE AN ON-SITE TRANSFORMER IS
 BEING INSTALLED BY FPL THE CONDUITS AND CONDUCTORS
 INCLUDING SERVICE ENTRANCE CONDUCTORS FROM SERVICE TO
 TRANSFORMER ARE BEING REQUIRED TO BE INSTALLED BY THE
 ELECTRICAL CONTRACTOR AND WILL BE THE RESPONSIBILITY OF
 THE OWNER. PLEASE KNOW AS MENTIONED ABOVE, IF CONDUITS
 AND CONDUCTORS ARE INSTALLED BY ELECTRICAL CONTRACTOR,
 THESE WILL BOTH FALL UNDER THE NEC AND ARE NEEDED TO BE
 SHOWN ON PLANS/SERVICE RISER.
 PLEASE OBTAIN LETTER FROM THE SERVICE PLANNER IF THESE
 WILL BE INSTALLED BY FPL.
 FBC 106.3.5.1.2, 106.1.2
  
 7) NOTE: PLEASE SEE THE CONDUIT SIZE IS MISSING FOR
 FEEDERS TO UNITS AND ARE UNABLE TO REVIEW AT THIS TIME
 FOR CODE COMPLIANCE. PLEASE SEE CONDUIT FILL TABLE IN
 CHAPTER 9 (C).
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE THE CONDUIT FOR HOUSE PANEL IS TOO
 SMALL FOR CONDUCTORS ARE SHOWN. NO CONSIDERATION HAS
 BEEN GIVEN FOR LENGTH AT THIS TIME.
 PLEASE ADJUST SIZE OF CONDUIT.
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE THE SERVICE METER CENTER IS BEING
 SHOWN AS 1160AMPS WHICH IS NOT A STANDARD SIZE PER
 240.6. PLEASE PROVIDE THE STANDARD SIZE OF EQUIPMENT.
 FBC106.3.5.1.2
  
 10) PLEASE SEE THE METER CENTER DOES NOT INDICATE ANY
 MAIN AS REQUIRED PER 230.70, 230.71.
 FBC 106.3.5.1.2
  
 11) PLEASE SEE NO AIC RATING(S) FOR MAINS AND BREAKERS
 ARE INDICATED AS REQUIRED.110.9, FBC 106.1.2,
 106.3.5.1.2
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE # 23
 REQUESTED COMPLETED LOAD CALCULATIONS WHICH WERE
 SUBMITTED HOWEVER PLEASE SEE 422.13 AS THE WATER
 HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD UNDER THE
 NEW CODE AND IS REQUIRED TO BE FIGURED AT 125%.
 PLEASE ADJUST CALCULATIONS.
 FBC 106.3.5.1.2
  
 13) NOTE: PLEASE SEE PREVIOUS NOTES #14 AND #28 AS
 ROOMS ARE AREAS NEEDED TO BE SHOWN ON PLANS,
 SPECIFICALLY DINING AREAS/ROOMS. PLEASE SEE AS
 PREVIOUSLY NOTED THE DINING AREAS AND/OR ROOMS SHALL BE
 ON ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS.
 PLEASE SEE E-3 UNIT B OPTION AS THE DINING RECEPTACLES
 ARE BEING SHOWN ON A GENERAL LIGHTING CIRCUIT WHICH IS
 NOT PERMITTED.
  
 14) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL
 SERVICE IS OF CONCERN. PLEASE SEE BASED ON THE SIZE OF
 SUCH EQUIPMENT AND BASED ON THE SCALE AND LOCATION AS
 SHOWN ON PLANS THERE SEEMS THERE WILL BE AN ISSUE FOR
 MINIMUM WORKING CLEARANCES AND PROTECTION OF EQUIPMENT.
 AS THE LOCATION HAS A DRIVEWAY/PARKING AREA IS RIGHT IN
 FRONT OF EQUIPMENT, NOT ONLY WILL THE EQUIPMENT REQUIRE
 MINIMUM CLEARANCES, BUT ALSO PROTECTION BY BOLLARDS TO
 PREVENT DAMAGE. PLEASE PROVIDE MINIMUM CLEARANCES,
 BOLLARD DETAIL, SITE DETAIL INCLUDED WITH THE ELEVATION
 DETAIL.
 PLEASE SEE BASED ON SCALE THE EQUIPMENT AS THIS IS VERY
 LARGE IN NATURE MAY PROTRUDE INTO DRIVE AREA.
 110.26
  
 15) NOTE: PLEASE PROVIDE INFORMATION AND ELECTRICAL
 PLANS FOR HOUSE PANEL AND EQUIPMENT.
 PLEASE SEE THAT NO PANEL SCHEDULE WAS SUBMITTED WITH
 OVER CURRENT PROTECTION, CIRCUITS, CONDUCTORS ETC.
 PLEASE SEE NO ELECTRICAL PLANS WERE SUBMITTED SHOWING
 LOCATION OF ELECTRICAL ON HOUSE PANEL.
 FBC 106.3.5.1.2
 NEC 2005 240.4, 310.16 ETC
  
 16) NOTE: PLEASE SEE 408.4, PLEASE PROVIDE MORE
 SPECIFIC DESIGNATIONS ON CIRCUITS AS SHOWN ON PANEL
 SCHEDULES.
 PLEASE SEE THE USE OF * GENERAL LIGHTING* SHOULD SHOW
 OR INDICATE THE ROOMS AND AREAS IN WHICH THESE CIRCUITS
 FEED. FOR EXAMPLE: BEDROOM #2 LIGHTING, LIVING ROOM
 LTS/RECEPTS ETC.
 THIS WAS A CHANGE IN THE 2005 CODE WHICH REQUIRES MORE
 SPECIFIC DETAILS.
 PLEASE ALSO SEE THE CIRCUITING AS SHOWN FOR UNIT *B*
 INDICATES CIRCUITING TO PANEL *A*.
 THESE DESIGNATIONS SEEM TO BE A MISPRINT AND SHOULD BE
 *B-3*, B27, B21 ETC.
 408.4.
 FBC 106.3.5.1.2, 106.5
  
 17) NOTE: PLEASE SHOW ON SITE ELECTRICAL PLANS THE
 LOCATIONS OF ALL CONDENSING UNITS, DISCONNECTS AND GFI
 RECEPTACLES.
 440.11, 110.26, 210.63, 210.8
 FBC 106.1.2
  
 18) NOTE: PLEASE SEE PREVIOUS NOTE #24 FOR 210.52.
 THERE IS STILL SOME RECEPTACLES MISSING AND NOT LOCATED
 AS REQUIRED PER 210.52.
 PLEASE SEE SOME OF THESE ARE REDLINED ON ONE OF THE SET
 OF PLANS.
 PLEASE SEE MISSING RECEPTACLES WITHIN 6FT OF DOORWAY
 OPENINGS.
 PLEASE ALSO KNOW THAT PERMANENT RAIL AREAS ARE
 CONSIDERED WALL SPACE.
  
 19) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** ONCE AGAIN AS THERE ARE SOME ITEMS NOT YET SUBMITTED
 FOR REVIEW THERE MAY BE NEW COMMENTS GENERATED ON THE
 NEXT REVIEW AS THESE ITEMS CAN NOT BE REVIEWED AT THIS
 TIME.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]